This dialog box includes the following areas and tabs:
See Common Tabs for information on the Location, Comments, Hyperlinks, Media Gallery, or Collected Data tabs.
Figure 1: MCC Data Dialog Box
Option | Description |
---|---|
ID Name |
Uniquely identifies the equipment item. The program automatically assigns a name, but you can change it, if needed. The name can be up to 16 characters long. For MCCs, the program automatically assigns the names MCC-1, MCC-2, MCC-3, and so on. |
Base kV | The base kV of the MCC. MCC’s are modeled like a bus in many ways. You can connect cables, busways or transformers to it, and perform fault calculations. |
Spreadsheet View and Configure | See Spreadsheet View for information about these options. |
Lock Auto-Sizing | When this check box is selected, this item cannot be automatically sized using SmartDesign™ (the auto-design feature). |
These are the specifications for the MCC including the bus.
Figure 2: Incoming Tab
Option | Description |
---|---|
Incoming Device Type |
You can select the type of incoming protective device type for the MCC. The choices available are:
|
Incoming Branch | Select the incoming branch equipment such as cables, transformers or busways. All the branches connected to the MCC in the one-line are displayed. |
Incoming Device Settings | Opens the data dialog for the main fuse or main breaker specified as the incoming device type. See Low Voltage Breaker Data or Fused Switch Data for more information. |
This is a spreadsheet listing similar to the Device Library. When you place a new MCC on the one-line, the first time you open its database dialog and click on the Description tab, EasyPower displays the MCC Spreadsheet Creation Wizard which enables you to select the number of rows you want. Clear the check box at the bottom of the Wizard dialog if you don't want it to appear with each new MCC. You can insert or append new rows in the spreadsheet if you need them later.
Figure 3: MCC Spreadsheet Creation Wizard Dialog Box
Figure 4: Description Tab of MCC Data Dialog Box
Note: When you click on the Description tab, additional buttons become available on the MCC Data dialog box toolbar. Some of these buttons are the same as those in the Device Library (see EasyPower Device Library) and they offer another way to add rows if the Wizard is not used.
Option | Description |
---|---|
MCC Library |
The list contains all of the same schedules as the Device Library. To enter a listing other than those contained in the list, create a new page in the MCC section of the Device Library. See EasyPower Device Library for more information. |
Schedule | This list enables you to specify which Device Library Schedule your chosen Library Load spreadsheet is located in. To enter a listing other than those contained in the list, create a new page in the MCC section of the Device Library. See EasyPower Device Library for more information. |
Export | The spreadsheets can be exported to metafiles (.WMF) or delimited database text files (.CSV). Export is beside the Print button on the MCC/Panel dialog box toolbar when the viewing the Description tab. |
Note: The Section Space and Equipment Name are not necessary for calculation purposes but are used to match the way they are organized in the MCC.
Option | Description |
---|---|
Section Space | Enter the location of the individual bucket in the MCC. Typical entries would be 1A, 1B, 2A, 2B, 2C, and so on. |
Equipment Name | Enables you to identify each piece of equipment. |
Library Load | This list corresponds directly to the Library Load column in the Device Library. After you have made selections in the MCC Library, Schedule and Library Load fields, all of the data cells that follow are automatically filled in when you click on another cell. You can also double-click on the cell to enter something different than what is listed. |
Status | The third column is a toggle "On/Off" to indicate if this particular item is currently connected to the MCC schedule. This affects the power flow and short circuit current contribution. |
Load Type |
You can select different kinds of loads such as motors, loads, or sub-MCC/panel. Based on the load type selected, various analysis are possible. When you select a load type, the cells in the row that do not apply become unavailable. You might see a Data button indicating you need to enter data specific to the load type. Cells highlighted in red require data in order to perform any analysis. The following load types are available:
Note: Motor FLA for 3-phase motors is calculated as follows. For U.S. units, the NEC table FLA values are used. For metric units, motor FLA is calculated as Motor kW/(Motor Eff * Motor power factor * Equipment kV * SQRT3). |
The rest of the fields correspond directly to those in the Device Library. MCCs are validated upon creation. That means that if you create an MCC and do not input any data, you can still go into an analysis focus without receiving an error message. However, after you create a row in this spreadsheet, you will not be able to enter an analysis focus until all required data is input. The cells which require data for analysis are highlighted in red.
If you are making a custom entry, you will notice that many of the data cells contain lists of items. Some of the cells have bold headings, and when they are selected the Calculate button becomes active. Clicking it calculates the data for those cells. You can select several cells at a time before clicking Calculate. For instance, clicking on the header itself selects the entire column.
Because the MCC is a library, along with the Calculate button, all of the other editing features are identical to those listed in the customizing section for the Device Library. See Customizing the Device Library for more information.
Use Spreadsheet View to configure the columns that appear in the spreadsheet. You can create new configurations that display only selected columns.
To create a new configuration, click Configure. In the Database Print Config dialog box, type the new configuration name in the Configuration box, and select the desired column headings in the Columns pane.
Use the Select All check box to include all the columns, or Clear All to clear all columns and select only those you want to see.
Use Delete to remove the selected configuration.
Close saves your changes and closes the dialog box.
Figure 5: Database Print Config Dialog Box
If you have multiple configurations saved, you can display the desired configuration by selecting it in the Spreadsheet View list.
To export an MCC or panel schedule, click Export in the toolbar of the MCC or panel data dialog box. This opens a new dialog box where you can specify location and file name of the file you are exporting, and you can select whether all MCCs and panels are to be exported, or only the selected one.
Figure 6: Export Dialog Box for an MCC or Panel Schedule
Option | Description |
---|---|
Save as type | You can save the schedule as a CSV (spreadsheet) file or as a WMF (picture) file. |
Print Range |
Choose one of the following.
|
Export All MCCs/Panels | When clear, only this MCC or panel is exported. When this check box is selected, all the MCC and Panels are exported. |
The Summary tab of MCC Data dialog box provides the total load on the MCC and the load that must be used in designing.
Figure 7: Summary tab of MCC Data Dialog Box (U.S. Units)
Figure 8: Summary tab of MCC Data Dialog Box (Metric Units)
Option | Description |
---|---|
Calculate Downstream Load | Calculates the total load on the MCC, taking into account the connected load, demand factors, and NEC code factors. |
Override with User Values | This check box enables you to enter data in the Total Downstream Load – kVA column. |
The spreadsheet has two sections – MCC Load and Including Downstream Load.
Option | Description |
---|---|
MCC Load This spreadsheet section provides the summary of the loads fed by the feeders of the MCC. The loads from the sub-MCC and sub-panels are not included in this section. |
|
Total kVA | This is the aggregate load. |
Total FLA | Total load in amps. |
Motor HP | The total HP for the items with "On" in the Status column of the Description section. |
Motor kVA >= 50 HP Motor kVA >= 37 kW |
The total KVA for connected items equal to or greater than 50HP (U.S. units) or 37 kW (metric units). |
Motor kVA < 50 HP Motor kVA < 37 kW |
The total KVA for connected items greater than 50HP (U.S. units) or 37 kW (metric units). |
VFD HP or kW |
Variable frequency drive HP (U.S. units) or kW (metric units). |
Static kVA | Total kVA of the loads. |
Capacitor kVAR | Total kVARs of all the capacitors |
(Calculations) | |
Connected | Connected kVA = [(SkW)2 + (SkVAR)2]1/2 |
Demand |
Demand kVA = [S(kW * DF)2 + S(kVAR * DF)2] ½ Where DF is the individual demand factor of each MCC circuit. |
Code Factors |
Code Factors kVA = [(kWL + SkW)2 + (kVARL + SkVAR)2]1/2 Where, kWL = Code Mult Factor * kW for largest motor in MCC. KVARL = Code Mult Factor * kVAR for largest motor in MCC. kW and kVAR are for the rest of the loads. The code multiplying factor is specified in Tools > Options > Equipment. |
Design |
Design kVA = Code Factors kVA * Design Factor The Design Factor is specified in Tools > Options > Equipment. |
Including Downstream Load This provides the sum of the loads fed by feeders inside the MCC and the sub-MCC and sub-panels. |
|
kVA | Total kVA load calculated. You can enter your own values in these fields by selecting the check box for Override with User Values. |
FLA | Total FLA load calculated. You can enter your own values in these fields by selecting the check box for Override with User Values. |
Figure 9: Short Circuit Tab of MCC Data Dialog Box (U.S.)
Figure 10: Short Circuit Tab of MCC Data Dialog Box (Metric)
Option | Description |
---|---|
kVA >50Hp kVA >37kW |
Total kVA of the motors which are greater than 50Hp (U.S. units) or 37kW (metric units). |
X"dv or Xlr | Is set at the default value for >50Hp (U.S. units) or 37kW (metric units). You can enter your own value and it applies to all the motors greater than 50Hp or 37kW. |
X/R Avg | Calculate fills this field using values from the spreadsheet. You can enter your own X/R average. |
KVA <50Hp kVA >37kW |
Total kVA of the motors which are less than 50Hp (U.S. units) or 37kW (metric units). |
X"dx or Xlr | Is set at the default value for <50Hp (U.S. units) or 37 kW (metric units) but you can change this. You can enter your own value and it applies to all the motors less than 50Hp or 37kW. |
X/R Avg | Calculate fills this field using values from the spreadsheet. You may enter your own X/R average. |
Calculate | Click to calculate the X/R averages for motors greater than and less than 50Hp (U.S units) or 37kW (metric units). |
Figure 11: Power Flow Tab of MCC Data Dialog Box
See MCC Elevation for information about this tab.
Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.
Figure 12: Harmonics Tab
Option | Description | |||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Load Type |
The default is Linear, indicating the equipment does not produce harmonics. Choosing Harmonic makes the item an harmonic source and makes other fields in this tab available to edit. Note:
|
|||||||||||||||||||||
Fundamental Amps |
Use to set the fundamental amps. The options are as follows:
To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box. |
|||||||||||||||||||||
Harmonic Spreadsheet |
Use the spreadsheet to enter the harmonic spectrum produced by this item. You can enter up to 30 different harmonics in each equipment item. In the spreadsheet, enter the Harmonic Number (such as 5 for the 5th harmonic), the Harmonic Current in percent of the Fundamental Amps, and the Current Angle. By indicating the current angle, you can simulate transformer phase shift effects on rectifiers so appropriate canceling can take place. The harmonic may be integer or non-integer. |
|||||||||||||||||||||
Library Load |
Common harmonic spectra may be entered from the device library. For instructions on how to enter your own spectra information, see Harmonics with Spectrum™. After selecting a particular device library spectrum from the Mfr and Type lists, click Import, and that spectrum is entered into the harmonic spreadsheet. |
|||||||||||||||||||||
Resistance Factor |
EasyPower offers two methods for calculating RH:
RH = RFund * H R-EXP RH = RFund * (1+ECF*H2)/(1+ECF) EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.
|
Figure 13: Arc Flash Hazard tab of MCC Data
Since the MCC can be analyzed like a bus, you can also obtain arc flash hazard assessment results for MCC. The arc flash tab is similar to that of bus data. However, the equipment type is forced to MCC/Panel, since an MCC cannot be another type. You can specify the trip time as available in the default library, enter the incident energy or you can enter the trip times in the fields. For detailed descriptions see Arc Flash Hazard Tab.
Figure 14: Accessories Tab
Option | Description |
---|---|
Accessories Description | The accessories for distribution equipment types can be specified in the panel, MCC, and bus dialog boxes. You can add or delete the accessory items as needed per equipment. Only the selected items are displayed in the schedule outputs. |
Meter Data | |
Note | An accessory note of up to 1,024 characters. |
Maximum Demand | The maximum demand load at this equipment. |
Power Factor | The power factor for the equipment. |
Reading Date | The date the meter was read or the information was gathered. |
kVA | |
Safety Factor | Percentage above the kVA that will be multiplied to calculate the new safety factor load. |
Load with Safety Factor | Load amount after calculating the safety factor. |
Added (New) Demand Load | User-specified load amount to add to the equipment. |
Total New Demand Load | Total of the load with safety factor and the added demand load. |
Total Amps | Amps based on the total demand load. |
See Common Tabs for information on the Location, Comments, Hyperlinks, Media Gallery, or Collected Data tabs.
Database Technical Reference | Common Tabs |
Media Gallery |
![]() |