Start Motor: When this check box is selected, it declares the selected motor as a starting motor in the current motor load. This only takes effect when you click Solve Motor. However, motor starting load is ignored when you click Power Flow. Note that the starting motor HP does not become part of the power flow solution.
Motor HP: Starting motor horsepower.
kVA/HP: The motor kVA rating per horsepower.
Locked Rotor Mult: Starting motor locked rotor multiplier. Typical values are 6 for induction motors and 4-5 for synchronous motors. The locked rotor multiplier is the reciprocal of the starting motor subtransient reactance (X"dv).
Start Power Factor: Starting motor power factor. This is typically between 12-15% for most machines.
|