Connectivity Rules
Disclaimer
This topic provides general rules for preparing EasyPower CSV import and export data. It is not an exhaustive list of all validation logic. Additional constraints may apply based on equipment type, configuration, project settings, and software version. For definitive validation, always refer to the EasyPower import validation messages and adjust your CSV data accordingly.
Core Model - Nodes, Branches, and Device References
Buses represent the network's connection points, or nodes. Connectivity throughout the system is primarily expressed by referencing the Bus ID. Certain types of equipment, such as panels, MCCs, ATS, and tool points of connection (POC) can also behave as connection points, though with specific limitations. To handle these variations, EasyPower uses the Bus Type column in the CSV data to clarify what kind of connection it is.
Other equipment either:
-
Connects to one bus (one-terminal): utilities, loads, shunts, etc.
-
Connects between two buses (two-terminal branch): cables, busways, 2W transformers, etc.
-
Connects between three buses (three-terminal branch): 3W transformers.
-
Attaches onto existing equipment (attachments): CTs, meters, relays.
Some types also allow an optional Device ID / Device Type at a connection end. This is used to indicate that the connection is made through a protective device mounted on that bus (for example, a cable feeder connected through a breaker on a panel bus).
Primary Connectivity Rules (What Can Connect to What)
In EasyPower, only certain types of equipment can connect to each other. These allowed pairings are listed in Allowed Connections.
Where Connectivity is Specified
The table below lists the columns that define connectivity for each type.
|
Equipment Type |
Connectivity Columns |
||
|---|---|---|---|
|
2W Transformer Busway Cable |
|
||
|
3W Transformer |
|
||
|
AFD Inverter Rectifier UPS |
|
||
|
ATS |
Source Connection |
||
|
Battery Capacitor Filter Generator Load Motor Photovoltaic (PV) Shunt Utility |
To Bus ID To Device ID To Device Type |
||
|
CL Reactor Transmission Line |
|
||
|
CT Meter |
Connected Equipment ID Connected Equipment Type Conn Side |
||
|
Fuse HV Breaker LV Breaker Switch |
On Bus ID To Bus ID |
||
|
Zigzag Transformer |
From Bus ID From Device ID From Device Type |
How to Represent Connections
Two-Terminal Branch Elements (Cable, 2W Transformer)
-
Enter the appropriate data in the From Bus ID and To Bus ID columns.
-
If the type includes Bus Type columns, set them to a valid value (bus, panel, MCC, POC).
-
Optionally, to model a direct connection through a protective device on that same bus, enter the From Device ID / From Device Type and/or the To Device ID / To Device Type.
Important: Device ID / Device Type does not replace the bus. It only indicates the branch is connected through a protective device that is mounted on that same bus (same end). If you don’t have a protective device at that end, leave Device ID / Device Type blank.
Protective Devices (LV Breaker, HV Breaker, Fuse, Switch)
-
On Bus ID is the bus the device is mounted on (source-side bus).
-
To Bus ID is optional:
-
If To Bus ID is entered, the device is modeled as a bus-to-bus connection, meaning the device is a tie or main device.
-
Only one bus-to-bus protective device (a "main" or "tie" device that directly connects two buses) is allowed per bus.
-
If To Bus ID is blank, the device is a device-only equipment item that may be referenced from other equipment rows using the Device ID / Device Type to indicate a direct connection through that device.
One-Terminal Sources and Loads (Utility, Generator, Motor)
-
Use the To Bus ID (and Bus Type if present) to place the equipment on a bus.
-
Optionally, use To Device ID / Device Type to indicate the piece of equipment it is directly fed through (for example, a switch or disconnect).
3W Transformers
-
3W Transformers use separate bus and device columns per winding (Primary / Secondary / Tertiary).
Instrumentation (CTs, Meters)
-
CTs and meters attach to an existing piece of equipment by specifying the Connected Equipment ID / Connected Equipment Type.
-
Conn Side indicates which terminal or winding side of the connected equipment is instrumented (From or To the Primary/Secondary/Tertiary side).
-
A maximum of 6 CTs can be attached per branch side.
-
A maximum of 1 meter can be attached per branch side.
-
Meters cannot be connected on ground lines.
Secondary Connectivity Rules (Topology Integrity Constraints)
In addition to Allowed Connections, EasyPower applies secondary rules that prevent ambiguous or physically invalid topologies. The most common constraints are:
Endpoint Completeness and Consistency
-
Every connection end must identify a bus-like equipment (Bus ID, and Bus Type if required by that type).
-
If a Device ID / Device Type is supplied at an end, that device must exist and must be mounted on the same bus identified for that end.
-
Do not specify a Device ID / Device Type without also specifying the corresponding Bus ID (and Bus Type when present).
Direct-Connection Cardinality
-
A bus can have many connected items.
-
A device terminal that is referenced using Device ID/ Device Type can be used by only one directly connected equipment item.
A cable can be directly connected to a breaker, but that breaker cannot also have a different cable directly connected on the other side. In CSV terms, the breaker should appear as a From Device / To Device endpoint in at most one branch element record. If you need multiple outgoing connections, insert a bus and connect multiple branches to that bus instead.
Avoid Device-Only Chains
-
Do not model connections as device-to-device without buses (for example, cable end to breaker with no bus). Buses are the nodes; devices are associated with buses or defined as bus-to-bus elements.
-
To model device-only chains, bypass the limitation of one tie or main device per bus by inserting a short busway or cable between them (their impedances will be negligible).
Multi-Terminal Devices: One Direct Attachment per Terminal
-
For input and output devices (such as AFDs, UPSs, inverters, or rectifiers) and transformers, treat each terminal (Input, Output, Primary, Secondary, Tertiary) as a distinct connection point that should not have multiple direct attachments without an intermediate bus.
Examples
|
Example 1: Cable Feeder Protected by an LV breaker |
|||
|---|---|---|---|
|
Type |
Key Fields |
Sample Values |
Meaning |
|
LV Breaker |
On Bus ID To Bus ID |
On Bus ID = BUS-1 To Bus ID = (blank) |
Create a breaker mounted on bus BUS-1 (breaker-only; not bus-to-bus). |
|
Cable |
From Bus ID From Bus Type From Device ID From Device Type To Bus ID To Bus Type To Device ID To Device Type |
From Bus ID = BUS-1 From Bus Type = Bus From Device ID = BUS-1-BKR-01 From Device Type = LV Breaker To Bus ID = LOAD-1 To Bus Type = Bus To Device ID = (blank) To Device Type = (blank) |
The cable starts at bus BUS-1 and is directly connected through breaker BUS-1-BKR-01, then lands on LOAD-1. |
|
Example 2: Breaker as a Bus-to-Bus Connection |
|||
|---|---|---|---|
|
Type |
Key Fields |
Sample Values |
Meaning |
|
LV Breaker |
On Bus ID To Bus ID |
On Bus ID = SWGR-A-MAIN To Bus ID = SWGR-A |
The breaker itself connects SWGR-A-MAIN to SWGR-A. The breaker becomes the unique tie/main breaker of SWGR-A. |
|
Example 3: One-Terminal Load (Motor) Attached to a Bus Through a Switch |
|||
|---|---|---|---|
|
Type |
Key Fields |
Sample Values |
Meaning |
|
Motor |
To Bus ID To Device ID To Device Type |
To Bus ID = MTR-1 To Device ID = MTR-1-DS To Device Type = Switch |
Motor is on bus MTR-1; the optional device fields indicate it is fed through switch MTR-1-DS on that same bus. |
Practical Import Tips
-
IDs must match exactly between types including spaces and punctuation. Keep IDs unique across equipment types.
-
Cross-referenced equipment must exist. If a row references a Bus ID or Device ID, that target must exist either in the one-line already or in the same CSV import set.
-
When in doubt, connect via a bus. Buses are the safest way to fan out multiple feeders and avoid violating the direct-attachment rules.
More Information
- Important Import Considerations
- Import Limitations
- Supported Import Fields
- Allowed Connections
- Import Data From an Individual CSV File
- Import Data From a Combined CSV File
- Import Data From a Zipped Individual CSV File
- Combined Versus Individual File Comparison
- Export Data from EasyPower
- Export to Individual CSV Files
- Export to Combined CSV Files
- Export Data Templates from EasyPower
- Export Data Templates to Individual CSV Files
- Export Data Templates to Combined CSV Files