Tutorial - Revit® Integrator (EasyPower Only) For Revit 2024

Note: This tutorial is for Revit 2024. If you are using an earlier version of Revit, see Tutorial - Revit® Integrator (EasyPower Only) For Versions Prior to 2024.

This tutorial describes how you can use Revit Integrator if you do not have Revit installed but want to import an exported Revit file into EasyPower. For example, you might use this if a Revit electrical designer has provided you with a Revit export file on which you need to run some design or analysis tasks. You can then export the changes to a file that a Revit electrical designer can import back into Revit.

Import the Revit File

After a Revit electrical designer creates an export file from the Revit project, you can import that file into EasyPower to automatically create a one-line model. To import the Revit file, do the following:

  1. In EasyPower, select File > Import > Import from Revit® Integrator.
  2. The number 1 is next to the File tab. The number 2 is next to the Import command. The number 3 is next to the Import from Revit Integrator command.

  3. On the Input File tab, click Browse to select the import file.
  4. The Import Revit Model dialog box is shown. The Input File tab is selected. The Browse button is highlighted.

  5. Browse to C:\Users\{username}\Documents\EasyPower 26.0\Onelines\Samples\Revit and select the Snowdon Towers Sample Electrical-Rev1.rvt2ezp file, and then click Open. This is a sample file that represents a file you might receive from a Revit electrical designer.
  6. The Revit sample file is selected in the Open dialog box.

  7. Click Mapping. For this example, we will use the Default Revit mappings, but notice that you can also create custom Revit mappings and create new configuration files here. This gives you additional control over how data is imported and lets you create configuration files that you can reuse in future imports.
  8. The Import Revit Model dialog box is shown. The Mapping tab is selected. The Default Revit mappings option is selected.

  9. Click One-line Target. For this example, we will select Create new one-line, but notice you can also merge the import data with a current one-line.
  10. The Import Revit Model dialog box is shown. The One-line Target tab is selected. The Create new one-line option is selected.

  11. If you click Summary, the program displays your import settings, but you can also just click Import at this point.
  12. The Import Revit Model dialog box is shown. The Summary tab is shown.

  13. EasyPower displays the one-line it created from the Revit project. The program also creates a report that describes any issues that were discovered. To view the report, click Window > Import Results Report.
  14. The one-line created from the import is shown.

    The Import Error Report is shown.

View the Imported Revit Data

For each item on the one-line, you can view the data that was imported by selecting the Collected Data pane in the equipment data dialog box, and then clicking the Collected Data tab.

The Collected Tab on the Bus Data dialog box is shown.

Perform Design and Analysis in EasyPower

At this point, you can perform design changes and analysis on the one-line. This includes performing auto design, performing short circuit and arc flash analysis, and calculating voltage drop in power flow. For information on those features, please refer to the additional tutorials. Note that you may need to add additional components (such as a utility power source) and input additional data (such as transformer impedances) to be able to perform analysis.

Export to Revit

After you have made changes to your EasyPower one-line, you can export the changes into a file that someone can then import into Revit. To create the export file in EasyPower:

  1. In the Database Edit focus, click File > Export > Export to Revit® Integrator.
  2. In the Configure Revit Export dialog box, select the items you want to export. Then, click OK.
  3. Note: Power Flow Voltage Drop is only available if you run a power flow analysis and perform voltage drop calculations.

    The Configure Revit Export dialog box is shown, with options for Analysis Results, Voltage Drop, and Equipment Sizing.

  4. The program asks you for a file name and location. You can use whatever name you like, but the file must have an .ezp2rvt extension. Make note of the file location, and then click Save.
  5. The custom file with an ezp2rvt extension is shown in the Save As dialog box.

You can now send the export file to a Revit electrical designer, who can then import the file you created into Revit.

Conclusion

This has been a brief overview of EasyPower’s Revit Integrator. The EasyPower Help topics cover this and other features in greater depth. To open Help, click  Help in the upper-right corner of the EasyPower window or press F1.