To select the short circuit calculation method, in the Database Edit focus, select Tools > Options > System, and select the desired standard in the SC Calculation Method box. You can also select the units and symbols appropriate for the selected standard.
Figure 1: Setting Short Circuit Method
To set the IEC Short Circuit calculation method, in the System tab of the Options dialog box, select the following:
Voltage C Factor table | ||
---|---|---|
Voltage Level |
Cmax |
Cmin |
Low Voltage ( < 1 kV) |
1.05 |
0.95 |
High Voltage ( > 1 kV) |
1.1 |
1 |
IEC Short Circuit Reference | |
IEC Short Circuit Options |