You are here: Tutorials > Short Circuit Analysis

EasyPower® Tutorial - Short Circuit Analysis

In this tutorial, you will be shown how to use several of EasyPower’s short circuit analysis features.

Short Circuit Focus

To run short circuit analysis, you must be in the Short Circuit focus.

  1. Open the Simple.dez file located in the EasyPower Samples folder. Click Maximize to fill your screen with the one-line.
  2. Click Short Circuit to open the Short Circuit focus.

Calculating Fault Currents

Double-click on BUS-3. The bus turns light blue and displays fault currents in symmetrical kilo-amps. As shown in Figure 1, the motor contributes 0.863kA and the cable 4.481kA to the fault. The total bus fault current, shown at a forty-five degree angle, is 5.344kA.

Figure 1: Calculating Fault Currents

There are several different methods to fault buses while in Short Circuit focus:

Remote Voltages and Currents

  1. Fault BUS-3 again.
  2. Select BUS-1 by clicking on it. With the SHIFT key pressed, also select BUS-2.
  3. Click Remote V/I. The remote currents are 0.896kA on the primary side of the transformer and 4.481kA on the secondary side (as shown in the figure below). The remote voltages, shown at a forty-five degree angle, are 0.643pu on BUS-1 and 0.000pu on BUS-2.

  4. Figure 2: Remote V/I

Changing the ANSI Standard Time Interval

ANSI Standards list three distinct time intervals for short circuit currents. These are momentary (½ cycle), interrupting (5 cycle), and 30 cycle. By default, EasyPower displays the momentary currents, as indicated by Momentary selected in the toolbar.

Unsymmetrical Faults

The currents calculated to this point have been 3-phase currents. EasyPower also calculates unsymmetrical faults. According to convention, single line-to-ground fault calculations assume the A-phase is faulted. For double line-to-ground and line-to-line faults, convention says that phases B and C are faulted. Refer to Elements of Power System Analysis by William D. Stevenson, Jr. for examples of unsymmetrical fault calculations.

Single Line-to-Ground Faults

  1. Click Interrupting and 30 Cycle to remove those selections, and leave Momentary selected.
  2. Click Line to Ground.
  3. Fault BUS-3 again. The currents will show zero (see figure below). This is because the transformer (delta-delta connection type) and motor are not grounded. (By default, EasyPower displays A-phase currents.)


    Figure 4: Single Line-to-Ground

Double Line-to-Ground Faults

  1. Click Double Line to Ground. The green dots in the button indicate ground fault.
  2. In the message that is displayed, click Yes to fault the B-phase line rather than the A-phase. All faults will now be double line-to-ground faults.
  3. Double-click on BUS-3 again. The B-phase double line-to-ground fault currents are displayed (see figure below).


    Figure 5: Double Line-to-Ground

Line-to-Line Faults

  1. Click Line to Line. Faults are now line-to-line faults. The yellow dots in the button indicate this is not ground fault.
  2. Fault BUS-3 again to display the B-phase line-to-line fault currents (see figure below).


    Figure 6: Line-to-Line Fault

Text Reports

  1. Click SC Reports from the ribbon.
  2. In the dialog box, select the Create HV & LV Momentary (½-Cycle) Reports check box on the upper left and then click OK.
  3. Click 3-Phase to return to 3-phase fault calculations.
  4. Click Fault Bus(es). A high voltage momentary text report window is created. You can view this report either by selecting HV Momentary Report for ‘simple.dez (Base case)’ from the Window button or by double-clicking on the window icon created in the lower left corner. Your text report will look similar to that in the figure below.


    Figure 7: Short Circuit Text Report

  5. You can return to the one-line by selecting Simple from the Window menu.

Other Options

  1. Click SC Options from the ribbon and select the One-line Output tab.

    In this dialog (shown in the figure below) you can specify asymmetrical fault currents to be displayed on the one-line. You can also show fault currents in Per-Unit or MVA units and remote voltages in kV units.


    Figure 8: Short Circuit One-line Output Dialog Box

  2. Select the Control tab.

    Here you can specify other short circuit settings for your fault calculations. These changes take effect on all subsequent faults after closing this dialog box.

Conclusion

This has been a brief overview of EasyPower’s short circuit program. The EasyPower User’ Manual and Help system cover these and other short circuit features in greater depth.

www.easypower.com

EasyPower, LLC

7730 SW Mohawk St.

Tualatin, OR 97062

(503)655-5059

techsupport@easypower.com

feedback@easypower.com

EasyPower Version 9.6

Copyright © 1991-2014 EasyPower, LLC. All Rights Reserved.

Help was last updated on 8/26/2014