All power flow equations are non-linear and require an iterative technique to solve. A wide range of data input values that increase the chance of numerical round off are inherent in many systems. For these reasons, some power flows may fail to converge. The following are some helpful hints in troubleshooting a failed power flow case.
Loading which is too high. Check for decimal place errors, remembering that EasyPower input data is in MVA not kVA.
Transformer taps or motor kV's which may be off by a decimal point. A transformer MVA may also be entered too low, or the motor HP too high.
Look for these problems in the area (within two buses) of the bus with the greatest mismatch. After you feel you have checked this area thoroughly, move onto the bus with the next-highest mismatch on the list, and so forth.
| Power Flow Analysis |