Setting the Short Circuit Method

To select the short circuit calculation method, in the Database Edit focus, select Tools > Options > System, and select the desired standard in the SC Calculation Method box. You can also select the units and symbols appropriate for the selected standard.

Figure 1: Setting Short Circuit Method

To set the IEC Short Circuit calculation method, in the System tab of the Options dialog box, select the following:

Voltage C Factor table

Voltage Level

Cmax

Cmin

Low Voltage ( < 1 kV)

1.05

0.95

High Voltage ( > 1 kV)

1.1

1

More Information

IEC Short Circuit Reference  