Temporary Motor Control Center Data

Figure 1: Temporary MCC Data Dialog Box

Options Description

MCC Load

HP and Total kVA: These list the totals of the items which are connected to the MCC. If an item has "Off" in the status column of the Description tab library of the regular database dialog, it will not be included in this total.
Load Model

This indicates the choice made in the Power Flow tab of the regular database dialog box—either MCC Specifications or SCADA.

Scaling Factor

Provides an easy way of adjusting the total motor load used in determining power flows. By changing the scaling factor, the actual HP (total connected value) entered in the HP field can remain static. This reduces modeling errors and eliminates multiple databases for different contingencies.

Load Type

MCCs can be modeled for the power flow solution in several different ways.

  • Constant kVA: This is the most common model. It is conservative, and will result in slightly lower voltage values than would be measured on an actual system.
  • Constant Current: This model is generally not used in motor modeling. It more closely matches an induction motor's characteristics in the reactive component than other models, but is technically incorrect because kW is relatively constant throughout the voltage range for an induction motor.
  • Constant Impedance: This model is used for starting induction and synchronous machines, and closely matches motor characteristics during low voltages.
  • Constant kW + j Current: This model is a combination of the above models and more closely matches actual motor characteristics within normal operating voltages.

Motor Starting

Start Motor: When this check box is selected, it declares the selected motor as a starting motor in the current motor load. This only takes effect when you click Solve Motor. However, motor starting load is ignored when you click Power Flow. Note that the starting motor HP does not become part of the power flow solution.

Motor HP:  Starting motor horsepower.

kVA/HP:  The motor kVA rating per horsepower.

Locked Rotor Mult: Starting motor locked rotor multiplier. Typical values are 6 for induction motors and 4-5 for synchronous motors. The locked rotor multiplier is the reciprocal of the starting motor subtransient reactance (X"dv).

Start Power Factor:  Starting motor power factor. This is typically between 12-15% for most machines.

Tip: Click DB Info to view all of the item's database information.

More Information

Temporary Dialog Boxes  
Power Flow Analysis  
     

www.easypower.com

EasyPower, LLC

7730 SW Mohawk St.

Tualatin, OR 97062

(503)655-5059

techsupport@easypower.com

feedback@easypower.com

EasyPower knowledge base

EasyPower Version 9.8

Copyright © 2017 EasyPower, LLC. All Rights Reserved.

Help was last updated on 7/10/2017