This dialog box includes the following areas and tabs:
See Common Tabs for information on the Location, Comments, Hyperlinks, Media Gallery, or Collected Data tabs.
                
            
Figure 1: ATS Data Dialog Box
| Option | Description | 
|---|---|
| ID Name | 
                         Uniquely identifies the equipment item. The program automatically assigns a name, but you can change it, if needed. The name can be up to 16 characters long. For automatic transfer switches, the program automatically assigns the names ATS-1,ATS-2, ATS-3, and so on.  | 
                
| Base kV | Base kV for the ATS. An ATS has three buses as shown by the nodes in the symbol. Note that the bus must have a kV entered before equipment can be connected to the bus. Anything less than 1kV is considered low voltage, anything 1kV or more is high voltage. | 
                
            
Figure 2: Stability Tab
| Option | Description | 
|---|---|
| Enable ATS Model | Select the check box to enter stability information. | 
| Manufacturer (Mfr) | Provides a list of manufacturers available in the device library. If the desired manufacturer is not listed in the device library, you can add it to the library. | 
| Type | Equipment types available from the selected manufacturer. If the desired type is not listed, you can add it to the library. | 
| Model | Equipment models available from the selected equipment type. If the desired model is not listed, you can add it to the library. | 
                         Lib | 
                    Populates the table with equipment data from the library. See EasyPower Device Library for more information. | 
See EasyPower Device Library for more information.
                
            
Figure 3: Arc Flash Hazard Tab
| Option | Description | 
|---|---|
| AF For This Bus | 
                         Specify how you would like arc flash results determined for this bus. Calculated: When calculated is selected, Trip times for this bus and Working Distances sections become available. Excluded: Select to exclude the bus from arc-flash reports. Some examples of when excluded might be selected are buses that are on utility side (not worked on by company employees) but still modeled on the one-line and buses where energized work is not likely (splices). Forced To: When selected an additional cell will appear where you can enter the incident energy for this bus. The arc flash value incident energy entered for this bus is shown on the one-line and in the Arc Flash Hazard Report. This is typically used for buses where the NFPA-70E has stated a particular PPE level can be assumed if certain conditions exist. Particularly, 208 volt equipment fed by 125 KVA or smaller transformers.  | 
                
| AF Output For This Bus | 
                         This specifies whether to display results on the line side or the load side of the Main protective device of the bus equipment. If the arc flash hazards output for this bus needs to be different from the global option, use this field. The choices are: 
  | 
                
| Trip Times for this Bus | 
                         Select method for determining trip times for this bus by choosing on the following: 
  | 
                
| Working Distances | 
                         Specifies the working distances shown on the one-line and in the arc flash hazard report. 
 The units displayed are based on the units selected in Arc Flash Hazard Options on the System tab. 
  | 
                
| Orientation | 
                         This is the orientation of the bus with respect to a worker that may be exposed to arc flash. This is not related to the vertical and horizontal buses in MCC and Switchgear. Arc travels away from the source and extends from the tip of the conductors. Based on the orientation of the conductors, the incident energy can vary. This choice affects the calculations factor (Cf) used in the arc flash hazard equations. See Orientation for more information.  | 
                
| Labels to Print | Enter the number of labels you want to print for arc flash hazard analysis. If you enter "0," no labels will print. | 
| Comment | Use to add a comment to the arc flash label. | 
See Common Tabs for information on the Location, Comments, Hyperlinks, Media Gallery, or Collected Data tabs.
| Database Technical Reference | Common Tabs | 
| EasyPower Device Library | |
| Media Gallery | 
                         
                     |