"Steam Turbine Gov1 T1 is <= zero."
"Steam Turbine Gov1 T3 is <= zero."
"Steam Turbine Gov1 R is <= zero."
"Diesel Gov1 T1 is <= zero."
"Diesel Gov1 T2 is <= zero."
"Diesel Gov1 T5 is <= zero."
"Diesel Gov1 T6 is <= zero."
"Gas Turbine Gov1 R is <= zero."
"Gas Turbine Gov1 T1 is <= zero."
"Gas Turbine Gov1 T2 is <= zero."
"Gas Turbine Gov1 T3 is <= zero."
"Woodward Steam PID1 TB is <= zero."
"Woodward Steam PID1 TC is <= zero."
"Woodward Steam PID1 TD is <= zero."
"Simple Exciter K is <= zero."
"Simple Exciter TE is <= zero."
"Simple Exciter TB is <= zero."
"Simple Exciter EMax is <= EMin."
"IEEET1 Exciter KA is <= zero."
"IEEET1 Exciter TF is <= zero."
"IEEET1 Exciter TR is <= zero."
"IEEET1 Exciter TA is <= zero."
"IEEET1 Exciter TE is <= zero."
"IEEET1 Exciter E2 is < E1."
"IEEET1 Exciter S(E2) is <= S(E1)."
"IEEET1 Exciter VRMax is <= VRMin."
"IEEE AC6A KA is <= zero."
"IEEE AC6A TA is <= zero."
"IEEE AC6A TB is <= zero."
"IEEE AC6A TH is <= zero."
"IEEE AC6A TR is <= zero."
"IEEE AC6A TE is <= zero."
"IEEE AC6A E2 is <= E1."
"IEEE AC6A S(E2) is <= S(E1)."
"IEEE AC6A VRMax is <= VRMin."
"IEEE AC6A VAMax is <= VAMin."
"IEEE AC8B TR is <= zero."
"IEEE AC8B TDR is <= zero."
"IEEE AC8B TA is <= zero."
"IEEE AC8B TE is <= zero."
"IEEE AC6A TH is <= zero."
"IEEE AC6A S(E2) is <= S(E1)."
"IEEE AC8B VRMax is <= VRMin."
"IEEE AC8B VEMax is <= VEMin."
"Round Rotor Gen E2 is <= zero."
"Round Rotor Gen S(E2) is <= zero."
"Round Rotor Gen has improper saturation constants - 1."
"Round Rotor Gen has improper saturation constants - 2."
"Round Rotor Gen E2 is <= E1."
"Round Rotor Gen S(E2) is <= S(E1)"
"Round Rotor Gen X''d is <= Xl."
"Round Rotor Gen X''q is <= Xl."
"Round Rotor Gen X'd is <= Xl."
"Round Rotor Gen X'q is <= Xl."
"Round Rotor Gen Xd is <= X'd."
"Round Rotor Gen Xq is <= X'q."
"Round Rotor Gen T'do is <= T''do."
"Round Rotor Gen T'qo is <= T''qo."
"Round Rotor Gen Xd is <= Xl."
"Round Rotor Gen Xq is <= Xl."
"Round Rotor Gen T'do is <= zero."
"Round Rotor Gen T'do is <= zero."
"Round Rotor Gen T'qo is <= zero."
"Round Rotor Gen T''qo is <= zero."
"Round Rotor Gen H is <= zero."
"Round Rotor Gen Rated kV is <= zero."
"Round Rotor Gen Bus kV is <= zero."
"Round Rotor Gen MVA is <= zero."
"Salient Pole Gen E2 is <= zero."
"Salient Pole Gen S(E2) is <= zero."
"Salient Pole Gen has improper saturation constants - 1."
"Salient Pole Gen has improper saturation constants - 2."
"Salient Pole Gen E2 is <= E1."
"Salient Pole Gen S(E2) is <= S(E1)."
"Salient Pole Gen X''d is <= Xl."
"Salient Pole Gen X'd is <= Xl."
"Salient Pole Gen Xd is <= X'd."
"Salient Pole Gen X'd is <= X''d."
"Salient Pole Gen Xq is <= X''q."
"Salient Pole Gen T'do is <= T''do."
"Salient Pole Gen T'do is <= zero."
"Salient Pole Gen T''do is <= zero."
"Salient Pole Gen T''qo is <= zero."
"Salient Pole Gen H is <= zero."
"Salient Pole Gen Rated kV is <= zero."
"Salient Pole Gen Bus kV is <= zero."
"Salient Pole Gen MVA is <= zero."
Descripción (Description) - En algunos modelos, los datos de entrada se comprueban para el funcionamiento del modelo correcto a la inicialización. Esto es especialmente cierto cuando modelos particulares crearán división numérica por cero o una condición de retroalimentación positiva si las constantes caen dentro de un rango específico.
Soluciona (Fix) - Si aparecen estos errores, debe solucionarlos para realizar una simulación. Cambie los valores para que no activan el error, entonces representan valores que proporcionan una respuesta del modelo correcto.
Estabilidad dinámica | |
Generación de mensajes |