IEC Equipment Duty Calculations

This topic describes the equipment duty calculations for breakers and fuses when your system is set to use the IEC standard.

HV Breakers

Initial Duty

Breaking Duty

t0(s)

tmin(s)

0 < t0 <0.05

0.02

0.05 <= t0 < 0.1

0.05

0.1 <= t0 <=0.1

0.1

0.25 <= t0

0.25

LV Breakers

Breaking Capacity, Isym (kA)

Test X/R

Division Factor

4.5 <= Isym <= 6 0.943 1.5
6 < Isym <= 10 1.782 1.7
10 < Isym <= 20 3.294 2.0
20 < Isym <= 50 4.023 2.1
Isym > 50 4.966 2.2