This topic describes the equipment duty calculations for breakers and fuses when your system is set to use the IEC standard.
Where,
Ib – Breaking current at tmin
Ik” – Initial current
f – Frequency
to = Opening time of the breaker
tmin = Breaking time determined by the opening time of the breaker
t0(s) |
tmin(s) |
---|---|
0 < t0 <0.05 |
0.02 |
0.05 <= t0 < 0.1 |
0.05 |
0.1 <= t0 <=0.1 |
0.1 |
0.25 <= t0 |
0.25 |
Device current at tmin
Breaking Capacity, Isym (kA) |
Test X/R |
Division Factor |
---|---|---|
4.5 <= Isym <= 6 | 0.943 | 1.5 |
6 < Isym <= 10 | 1.782 | 1.7 |
10 < Isym <= 20 | 3.294 | 2.0 |
20 < Isym <= 50 | 4.023 | 2.1 |
Isym > 50 | 4.966 | 2.2 |
Device current (symmetrical)
Control Tab (IEC) |