Cable Data

This dialog box includes the following areas and tabs:

See Common Tabs for information on the Location, Comments, Hyperlinks, Media Gallery, or Collected Data tabs.

Figure 1: Cable Data Dialog Box (AC Cable)

Connection Information

Option Description
ID Name

Uniquely identifies the equipment item. The program automatically assigns a name, but you can change it, if needed. The name can be up to 16 characters long.

For cables, the program automatically assigns the names C-1, C-2, C-3, and so on.

From Bus The bus from which the cable connects, which must already exist on the one-line. You must be careful that the From Bus has the same base kV as the cable’s To Bus. For your reference, the From Bus base kV is displayed next to the bus name.
To Bus The bus to which the cable connects, which must already exist on the one-line. You must be careful that the To Bus has the same base kV as the cable’s From Bus. For your reference, the To Bus base kV is displayed next to the bus name.
Show Entire Line This box is selected by default and causes the entire line to be displayed. By clearing the check box, the line is only shown as a short section at each end with labels indicating the bus to which the other end is attached.

Style

The style of the line that appears on the one-line. This setting is specific to the selected item and overrides any default styles specified for the equipment.

Weight

The weight of the line that appears on the one-line. This setting is specific to the selected item and overrides any default weights specified for the equipment.

Lock Auto-Sizing While sizing cables with SmartDesign™ (the auto-design feature), the cable data is not changed if this field is selected. However, an auto-design report is created for the cable to show what would have been designed. Use this field to prevent cable data from being changed in SmartDesign™.

Specifications 1 Tab

Option Description
Unit Choose either U.S., CSA, Metric or Per Unit. If you choose Per Unit, all fields except those in the Impedance (PU) section become unavailable.
No/Phase Total number of cables modeled. The default of one (1) means one conductor per phase. Two (2) means two conductors in parallel per phase, and so on. When two or more conductors are in parallel, the impedance of the circuit is decreased by that factor. The impedances shown in the dialog box are for one conductor only, and are not based on the No./Phase field, so if you enter these values instead of using Calculate, make sure they are for one conductor only. This lets you easily check handbook values without additional arithmetic. The per-unit impedances listed in a database report considers the total number of conductors.
Type

Five different cable types can be modeled. Cable type is used in determining the impedance of the conductor.

  • 1/C - One conductor. Three separate conductors are used for a circuit, one each for A phase, B phase and C phase.
  • 3/C - Three conductor. This is the same as three separate conductors, except that the conductors are encased with an insulated overall outer jacket effectively forming one cable. The cable may or may not have an interstitial ground wire.
  • IAA - Interlocked armor aluminum. This is the same as the three conductor cable except that the outer jacket is made of aluminum instead of protective insulation. IAA is a generic term for describing any type of aluminum jacket including continuous sheath products such as Okonite CLX.
  • IAS - Interlocked armor steel. This is the same as IAA except that the outer jacket is made of steel instead of aluminum.
  • MAC - Messenger aerial cable. Messenger aerial cable is three separate conductors bundled together with a messenger cable easy hanging from poles. Because the conductors are held in a triangular fashion with the bundling, the impedance of this configuration is the same as for the 3/C cable.

Note: For Teck cables, select the CSA unit. For single conductor Teck, select 1/C and for 3-conductor Teck, select IAA for aluminum armor or IAS for steel armor. Look for Teck or Teck-90 in the Insulation type.

Insulation

US Low Voltage Insulation (1000 volts or less):

  • EPR - Ethylene Propylene Rubber.
  • PVC - Polyvinyl chloride.
  • RH - Heat Resistant Rubber, 75oC.
  • RHH - Heat Resistant Rubber.
  • RHW - Moisture and Heat Resistant Rubber. This is the 480 volt equivalent of EPR.
  • THHN - Heat Resistant Thermoplastic.
  • THWN - Moisture and Heat Resistant Thermoplastic.
  • THW - Moisture and Heat Resistant Thermoplastic.
  • TW - Thermoplastic insulated moisture resistant cable.
  • XHHW - Moisture and Heat Resistant Crosslinked Synthetic Polymer. This is the 480 volt equivalent of XLPE.

US High Voltage Insulation (Over 1000 volts):

  • XLPE - Crosslinked Polyethylene.
  • XLPE-133% - Crosslinked Polyethylene with 133% insulation.
  • XLPE-NJ - Non-Jacketed Crosslinked Polyethylene.
  • XLPE-NJ-133% - Non-Jacketed Crosslinked Polyethylene with 133% insulation.
  • XLPES - Shielded Crosslinked Polyethylene.
  • XLPES-133% - Shielded Crosslinked Polyethylene with 133% insulation.
  • EPR - Ethylene Propylene Rubber.
  • EPR-133% - Ethylene Propylene Rubber with 133% insulation.
  • EPR-NJ - Non-Jacketed Ethylene Propylene Rubber.
  • EPR-NJ-133% - Non-Jacketed Ethylene Propylene Rubber with 133% insulation.
  • EPRS - Shielded Ethylene Propylene Rubber.
  • EPRS-133% - Shielded Ethylene Propylene Rubber.
  • PILC - Paper Insulated Lead Sheath.
  • PILC-133% - Paper Insulated Lead Sheath with 133% insulation.

Insulation level

Denotes whether the selected insulation type has extra thickness for a higher level of insulation.

Examples include 100% or 133% for the selected insulation type.

Size Conductor size in AWG, MCM, or mm2. Cable size is used in determining the impedance of the conductor.
Conductor Material The conductor material (copper or aluminum).
Length Length of the cable in feet or meters.
Impedances
Impedances are described as Ohms/1000 feet, Ohms/KM or PU. Zero sequence impedances are described as the positive sequence impedance using a Z0/Z1 multiplier by Kaufmann1, specifically, on page 7.
R1

Positive sequence resistance.

The resistance values are used in power flow, ANSI short circuit, harmonics, dynamic stability and auto design analysis.

For IEC 60909 short circuit, separate resistance values are used. Maximum short circuit currents uses resistance at 20°C. Minimum short circuit currents use the resistance at the final conductor temperature at the end of the short circuit. EasyPower calculates these resistances based on the resistances R1 and R0 and the Field Temperature of Conductor from the Specifications 2 tab. If you enter the R1 and R0 values manually, be sure to set the Field Temperature of Conductor to get the appropriate resistances for IEC short circuit. The Database Browser shows the per-unit resistances for maximum and minimum short circuit currents.

X1 Positive sequence reactance.
R0

Zero sequence resistance. If you enter this value as zero (0.0), the positive sequence impedance is used.

The resistance values are used in power flow, ANSI short circuit, harmonics, dynamic stability and auto design analysis.

For IEC 60909 short circuit, separate resistance values are used. Maximum short circuit currents uses resistance at 20°C. Minimum short circuit currents use the resistance at the final conductor temperature at the end of the short circuit. EasyPower calculates these resistances based on the resistances R1 and R0 and the Field Temperature of Conductor from the Specifications 2 tab. If you enter the R1 and R0 values manually, be sure to set the Field Temperature of Conductor to get the appropriate resistances for IEC short circuit. The Database Browser shows the per-unit resistances for maximum and minimum short circuit currents.

X0 Zero sequence reactance. If you enter this value as zero (0.0), the positive sequence impedance is used.
Rating Conductor rating in amperes. If you use Calculate, this value is retrieved from the device library and is for one conductor. You need to input the proper rating. The 75(C) rating is shown, to indicate lug ratings, below the rating field if calculate is used to determine the rating (low voltage only). You can derate cable amp rating based on ambient temperature and the number of conductors in conduits or raceways by specifying the Ambient Temp and the Duct Config field in the Specification 2 tab of the dialog box. For the Ambient Temp derating to take effect, you need to specify the derating standard in Tools > Options > Equipment.
Calculate

Fills in computed values for the R1, X1, R0, X0, Xc, Xc0, and Rating (A) fields. You can override these values by typing in your own numbers. The calculations are based on the cable specifications and the type of ground circuit.1,2

Reference:
1 General Electric Wire and Cable Handbook, March 31 1983.
2 IEC 60228 Conductors of Insulated Cables, Third Edition 2004-11

Raceway Configuration
Type

Medium in which the conductor is supported or run (conduit, cable tray, air, or direct buried). If none is selected, the cable ampacity defaults to 10A.

Note: For buried conduits, you can apply the derating for ampacity in the Duct Config field on the Specifications 2 tab.

Material Raceway material, which can be either metallic such as steel, or non-metallic such as aluminum, PVC, IMT, or EMT. This value is used in determining reactances.

DC Cable Resistance Specifications

Figure 2: DC Resistance Specification

Option Description
Rdc (One way length) The DC resistance of the cable, specified in Ohms per 1000 feet and as the one way (not out and back) value. (Not applicable for AC cables.)
Rating (A) Ampacity of the DC Cable.

Note: Doubling of Cable Length—Since DC systems are not “balanced,” cable runs need to simulate the total out and back DC resistance. Thus, internally, all DC line lengths are doubled to properly simulate the total voltage drop correctly.

Specifications 2 Tab

Figure 3: Specifications 2 Tab of the Cable Data Dialog Box (AC Cable Shown)

Note: All fields have a substantial effect on conductor impedances when using the Calculate button.

Description Option
Field Temp of Conductor (C)

Temperature of the loaded conductor. This can be varied from 25C to 250C depending on the type of study being performed. Cable temperature is used in determining the resistance of the conductor. The resistance increases with the conductor temperature.

Note: This is not the ambient air temperature or the ground temperature.

Cond Spacing

Distance between the outside insulation or jacket edges of adjacent phase conductors. This will affect the reactance calculations. All three spacings are modeled as the same or as a GMD equivalent.

Note: This is not the center to center distance. See figure below.

Figure 4: Conductor Spacing: Zero Spacing (Left) and With Spacing (Right)

Ampacity Derating

Duct Config

This field allows for cable ampacity derating based on the number of conductors in the conduit, tray or duct. Select from D-1, D-2, and so on, which correspond to NEC Detail 1, NEC Detail 2, and so on, of the National Electric Code. If this field is left blank, a 1.0 multiplier is assumed for the ampacity calculations. The rating factors are stored in the standard device library and can be customized if needed. If you need to derate cables based on number of conductors in the conduit or tray, you can add to the library.

Figure 5: Cable Derating in the Standard Device Library

Figure 6: 11.5” X 11.5” Electrical duct bank. One electrical duct

 

Figure 7: 19” X 19” Electrical duct bank. Three electrical ducts

For a complete listing of duct configurations, please see article 310 in the National Electric Code.

Ambient Temp Ambient air temperature. This is used for ampacity derating based on the standard selected in Tools > Options > Equipment. You can choose US (based on NEC), CSA (based on CEC) or <None> in the Options. No derating is applied when the option is <None>.
 

Conductor Lay

(AC cable only)

Lay of the conductor, which affects the impedance. 3/C, IAA, IAS, and MAC configurations are always defined with a triangle configuration and zero spacing even if you choose a different configuration. Single conductor cables, however, can be in flat, triangle or a right triangle configuration with any spacing factor.
Conductor Form Conductor form is determined by the extrusion process of the copper or aluminum. Select either round or sectored.
Conduit Size & Num Size and number of conduits. This does not affect the impedance or ampacity calculations, but is stored as data. SmartDesign™ populates this field while automatically sizing the cables. The size appears in inches or millimeters depending on how Units are specified on the Specifications 1 tab.

Ground Wire Tab

Figure 8: Ground Wire Tab of the Cable Data Dialog Box

Option Description

Type

(AC cable only)

Ground conductor type (none, interstitial, separate, or as part of a group of conductors). This choice has an effect on the zero sequence impedance calculation. See Reference2 below for more information on ground impedance calculations.

None: No ground conductor.

    Interstitial: The ground wires in a three conductor cable (or IAA, IAS, CLX, TEC). Typically, there are three bare ground wires spaced evenly between the phase conductors.

Figure 9: Interstitial Ground

    Separate: A separate ground conductor in a conduit for a specific circuit.

Figure 10: Separate Ground

    Group: A ground conductor in a duct bank or tray that is used for multiple circuits.

Num Number of ground wires in the circuit. This value is for reference only and does not affect analysis.
Size

Ground conductor size. This value is for reference only and does not affect analysis.

Note: The size of ground wire may not have a direct influence on the effective zero sequence resistance (R0) and reactance (X0). Refer to Kaufmann’s paper2 on grounding. For steel conduits, ground currents flow through the conduit close to the outer surface because of skin effect.

Material Ground conductor material. This value is for reference only and does not affect analysis.
Insulation Type of insulation for the ground wire. Select <None> for bare conductor. This value is for reference only and does not affect analysis.

Reference:
2 Let's Be More Specific About Equipment Grounding, R.H. Kaufmann, General Electric Co., GER 1974

Neutral Wire Tab

All neutral wire fields are for reference only and do not affect analysis. Not applicable to DC cables.

Figure 11: Neutral Wire Tab of the Cable Data Dialog Box (AC Only)

Option Description
Num Number of neutral wires.
Size Size of the neutral wire.
Rating Amp rating of the neutral conductor. Enter amp rating based on size.
Material Neutral material type (copper or aluminum).
Insulated Whether or not the neutral conductor is insulated.

Harmonics Tab

Note: Not applicable to DC cables.

Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.

Figure 12: Harmonics Tab

Option Description
Resistance Factor

EasyPower offers two methods for calculating RH:

  • Resistance varying with a power of the harmonic (R-EXP):
  • RH = RFund * H R-EXP

  • Resistance varying with a percent eddy current factor (%ECF):
  • RH = RFund * (1+ECF*H2)/(1+ECF)

EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.

Typical Resistance Correction Factors

  R-EXP %ECF

Transformer

0.5-1.0

1.0-3.0

Utility

0.0-0.8

    -

Generator

0.3-0.6

    -

Line/Cable

0.5

    -

Reactor

0.5-1.0

0.8-3.0

Motor

0.2-0.4

    -

Fundamental Amps

Use to set the fundamental amps. The options are as follows:

  • Equipment Rating sets Fundm Amps to the equipment rating of the item described in the Specifications tab. 
  • User Specified activates the Fundm Amps field, enabling you to specify a value. 

To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box.

Other Tabs

See Common Tabs for information on the Location, Comments, Hyperlinks, Media Gallery, or Collected Data tabs.

More Information

Database Technical Reference Common Tabs
Media Gallery  
     

www.easypower.com

EasyPower, LLC

7730 SW Mohawk St.

Tualatin, OR 97062

(503)655-5059

techsupport@easypower.com

feedback@easypower.com

EasyPower knowledge base

EasyPower Version 10.0

Copyright © 2018 EasyPower, LLC. All Rights Reserved.

Help was last updated on 5/22/2018