Governor Models
Gas Turbine Governor
Figure 1: Gas Turbine Governor Model Block Diagram
Parameter |
Units |
Description |
---|---|---|
R |
pu |
Droop |
T1 |
Seconds |
Governor control time constant |
T2 |
Seconds |
Combustion chamber time constant |
T3 |
Seconds |
Exhaust temp measurement time constant |
AT |
pu |
Ambient temperature load limit |
KT |
pu |
Load limit gain |
VMax |
pu |
Governor control max |
VMin |
pu |
Governor control min |
DT |
pu |
Damping |
Woodward Diesel Governor
Figure 2: Woodward Diesel Governor Model Block Diagram
Parameter |
Units |
Description |
---|---|---|
R |
pu |
Throttle feedback gain (affects droop) |
T1 |
Seconds |
Control box time constant |
T2 |
Seconds |
Control box time constant |
T3 |
Seconds |
Control box time constant |
T4 |
Seconds |
Actuator time constant |
T5 |
Seconds |
Actuator time constant |
T6 |
Seconds |
Actuator time constant |
TD |
Seconds |
Engine firing delay time |
K |
pu |
Actuator gain |
TMax |
pu |
Max actuator torque |
TMin |
pu |
Min actuator torque |
Droop / Isoch |
|
Switch (droop mode or isochronous mode) |
Woodward Steam PID1 Governor
Figure 3: Woodward Steam PID 1 Governor Model Block Diagram
Parameter |
Units |
Description |
---|---|---|
TA |
Seconds |
Governor control time constant |
TB |
Seconds |
Governor control time constant |
TE |
Seconds |
Governor control time constant |
TC |
Seconds |
Actuator time constant |
TD |
Seconds |
Turbine time constant |
K |
pu |
Governor control gain |
PMax |
pu |
Max power output |
PMin |
pu |
Min power output |
Dr |
pu |
Droop |
More Information
Dynamic Stability | |
Stability Data Parameters |
![]() |