Motors

The design template for motor circuits is entered in this part of the library. A motor circuit consists of a motor, cable, and a protective device.

Option Descriptions
Option Description

kV

Rated kV for the motors. The motor rated voltage must be defined in the library. Use Add New to create new voltage levels. Each kV level has its own design template. The motor voltage in the one-line must be exactly equal to the voltage defined in the library for Auto-Design to work. A mismatch of voltage yields no results. You can add any number of voltage levels for motors. To view or edit data for any voltage level, select the kV first. To delete a kV value, delete all the cells in the spreadsheet for that kV.

Motor HP

Rated horsepower (HP) for the motor for which circuit is to be designed. The HP for the motor in the one-line must match the design library Motor HP. You must enter the Motor HP before you can enter other details for that circuit. Deleting the Motor HP deletes the details.

Note: The cables and protective devices in the motor circuits are designed as per the motor HP.

NEC FLA

Full-load current for the motor based on National Electric Code (NEC 2005), Table 430.250. The FLA is determined from motor voltage and size (HP).

FLAx1.25

This is NEC FLA multiplied by a factor of 1.25.

Protective Device (A)

Continuous current rating for the device protecting the motor circuit.

Device Type

Type of protective device such as fuse or circuit breaker. This field is currently used for database purposes only and is not used in calculations.

Phase

Details of the phase conductors for motor circuits.

No/Ph

Number of conductors in each phase.

Type

Core construction such as 1/C, 3/C, and so on.

Ins

NEC/UL insulation designation.

Size kCMIL

Size of conductor in AWG or kcmil.

Ins (C)

Maximum operating temperature for the cable based on insulation type. This is defined in the cable data library, and is automatically filled in once you select the cable details.

Cond Matl

Conductor material—either copper (Cu) or aluminum (Al).

Ground

Details of ground conductors for motor circuits.

No/Ph

Number of ground conductors.

Size kCMIL

Size of conductor in AWG or kcmil.

Raceway

Details of conductor raceway.

Type

Type of enclosure for cables, such as conduit, tray, air, burial, and so on.

Material

Material type for the enclosure, such as steel aluminum, PVC, and so on.

Conduit No.

Number of conduits.

Conduit Size (in)

Diameter of conduits in inches.

Ampacity

Current carrying capacity of the cables for continuous loads. The program automatically obtains the ampacity values from the cable library.

Terminal Ampacity @ 75 deg C

Ampacity for cable terminations. The program automatically computes the terminal ampacity from the cable ampacities.

More Information