IEC Impedance and X/R Calculations
| Model | Motor Type | Impedance and X/R Calculations | 
|---|---|---|
| Individual | Induction without AFD | 1) Calculate the MW per pole-pair by dividing MW by pole-pairs. 
 2) Calculate the X/R ratio of the motor. 
 Impedance is 16.7%. | 
| Group | Induction without AFD | Impedance and X/R are calculated as follows: 
 | 
| Individual or Group | Induction with AFD DC with AFD | Impedance is 16.7% and the X/R ratio is 10. | 
| Individual or Group | Synchronous Synchronous Condenser | Uses the ANSI default calculations for impedance and the X/R ratio. | 