Specifying Enclosure Size

You can specify the enclosure size shown on the one-line and in reports and work permits.

  • Default from Library: When selected, the program uses the enclosure size from the device library. The library provides typical values based on the equipment type and voltage.
  • User Specified: Selecting this option enables you to enter the enclosure size for the item. This enables you to get more accurate calculation results, assuming the correct dimensions are entered.
  • The units displayed are based on the units selected in Arc Flash Hazard Options on the System tab. For inches, the range is .01-1000. For millimeters, the range is 0.1 to 25,000.

The enclosure dimensions affect arc flash.

  • Arc flash is greatest for a 20 in. x 20 in. x 20 in. enclosure.
  • Arc flash decreases as the height or width dimensions increase.
  • In low voltage equipment with a height and width of less than 20 inches, arc flash decreases if the depth dimension is less than or equal to 8 inches.