AFD - Specifications Tab
| Option | Description | 
|---|---|
| 
                                                         Input AC Frequency  | 
                                                    
                                                         The fixed frequency on the input side. This is specified in the System tab of Options dialog box.  | 
                                                
| 
                                                         Output AC Frequency  | 
                                                    
                                                         The adjustable frequency on the output of the AFD. This affects the frequency of all equipment connected on the output of the AFD.  | 
                                                
| 
                                                         Rating  | 
                                                    
                                                         Rated Input kVA or the motor HP of the drive.  | 
                                                
| 
                                                         X/R  | 
                                                    
                                                         If the AFD is regenerative, this value is used to define the short circuit X/R ratio of the contribution delivered at the input of the AFD. The Calculate button uses an ANSI standard lookup table to fill in this value.  | 
                                                
| 
                                                         PF  | 
                                                    
                                                         The input power factor of the AFD for power flow simulations.  | 
                                                
| 
                                                         Efficiency  | 
                                                    
                                                         The efficiency of the AFD. This creates a real power increase from the output to the input of the AFD.  | 
                                                
| 
                                                         Input Side  | 
                                                |
| 
                                                         Diode / IGBT  | 
                                                    
                                                         This is currently IGBT only.  | 
                                                
| 
                                                         Non-regen / Regenerative  | 
                                                    
                                                         Select Non-regen to simulate a non-regenerative drive and Regenerative to simulate a regenerative drive (which includes a short circuit contribution on the input of the AFD).  | 
                                                
| 
                                                         Initial / Momentary Fault x FLA  | 
                                                    
                                                         The defined bolted fault level for the input of the AFD if it is regenerative. The label displayed is based on the IEC or ANSI option selected to Tools > Options.  | 
                                                
| 
                                                         Output Side  | 
                                                |
| 
                                                         IGBT / Thyristor  | 
                                                    
                                                         Select IGBT to model a source inverter on the output, or choose Thyristor to model a Thyristor output. This currently does not affect any calculations.  | 
                                                
| 
                                                         Fault x FLA  | 
                                                    
                                                         The fault current output of the AFD under a bolted fault condition.  | 
                                                
| 
                                                         Fault Time  | 
                                                    
                                                         The time that Fault x FLA is produced by the AFD under fault conditions  |