Cable - Harmonics Tab
Note: Not applicable to DC cables.
Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.
Figure 1: Harmonics Tab
| Option | Description | |||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 
                                                         Resistance Factor  | 
                                                    
                                                         
 EasyPower offers two methods for calculating RH: 
 RH = RFund * H R-EXP RH = RFund * (1+ECF*H2)/(1+ECF) EasyPower defaults all skin effect correction to R-EXP and a value of 0.5. 
  | 
                                                |||||||||||||||||||||
| 
                                                         Fundamental Amps  | 
                                                    
                                                         
 Use to set the fundamental amps. The options are as follows: 
 To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box.  | 
                                                