IEC Impedance and X/R Calculations
| 
                                                         Model  | 
                                                    
                                                         Motor Type  | 
                                                    
                                                         Impedance and X/R Calculations  | 
                                                
|---|---|---|
| 
                                                         Individual  | 
                                                    
                                                         Induction without AFD  | 
                                                    
                                                         1) Calculate the MW per pole-pair by dividing MW by pole-pairs. 
 2) Calculate the X/R ratio of the motor. 
 Impedance is 16.7%.  | 
                                                
| 
                                                         Group  | 
                                                    
                                                         Induction without AFD  | 
                                                    
                                                         Impedance and X/R are calculated as follows: 
  | 
                                                
| 
                                                         Individual or Group  | 
                                                    
                                                         Induction with AFD DC with AFD  | 
                                                    
                                                         Impedance is 16.7% and the X/R ratio is 10.  | 
                                                
| 
                                                         Individual or Group  | 
                                                    
                                                         Synchronous Synchronous Condenser  | 
                                                    
                                                         Uses the ANSI default calculations for impedance and the X/R ratio.  |