UPS - Specifications Tab
                                                
                                            
Figure 1: Specifications Tab
                                                
                                            
Figure 2: UPS Short Circuit Output Settings for IEC
| Option | Description | 
|---|---|
| 
                                                         UPS kVA  | 
                                                    
                                                         kVA rating of the UPS.  | 
                                                
| 
                                                         X/R  | 
                                                    
                                                         X/R ratio used for short circuit calculations at the output.  | 
                                                
| Short Circuit Output | |
| 
                                                         ½ Cycle / Initial  | 
                                                    
                                                        
 The value is entered as a multiple of the kVA rating. Example: A 500kVA/0.48kV UPS has a momentary short circuit contribution of 3000Amps. The short circuit capability in multiples of kVA rating is 4.988 (~5.0). [ multiple = sqrt(3)*3kA*0.48kV/500kVA.]  | 
                                                
| 
                                                         Interrupting / Breaking  | 
                                                    
                                                        
  | 
                                                
| 
                                                         30 Cycle / Steady State  | 
                                                    
                                                        
  |