Utility - Specifications Tab
See also: DC Utility Specifications Tab
                                                
                                            
Figure 1: Specifications Tab (3-Phase)
                                            
                                        
Figure 2: Specifications Tab (1-Phase)
| Option | Description | 
|---|---|
| 
                                                         Utility kV  | 
                                                    
                                                         The Utility kV field represents the maximum voltage between conductors in a utility supply. This value is used in calculation of per-unit impedance. This does not affect the power flow controlled voltage. The Utility kV displays line-to-line (LL) voltage for a 3-Phase or line-to-line connected single-phase utility that has the conductors AB, BC, or CA. For line-to-ground or line-to-neutral connected single-phase system such as AN, BN, or CN, the Utility kV is line-to-neutral (LN) voltage. For a 1PH-3W system, enter the line-to-line voltage.  | 
                                                
| 
                                                         Fault Duty Unit  | 
                                                    
                                                         Specifies the unit in which the short circuit information is entered. Any of the four following units may be selected: 
 See the Fault Duty Unit table below for more information.  | 
                                                
| 
                                                         Utility MVA Base  | 
                                                    
                                                         When Zpu is selected as the fault duty unit, you also need to specify the MVA Base of the utility for the per unit values.  | 
                                                
| 
                                                         3-Phase / 1-Phase Short Circuit  | 
                                                    
                                                         Used in determining short circuit reactance and resistance values for 3-phase faults and line-to-line faults. For a single phase utility this is the available fault value. See the Fault Duty Unit table below for more information.  | 
                                                
| 
                                                         SLG Short Circuit  | 
                                                    
                                                         Used in determining short circuit reactance and resistance values for single line-to-ground faults. See the Fault Duty Unit table below for more information.  | 
                                                
Fault Duty Units
| Fault Duty | Short Circuit Values | |
|---|---|---|
| 
                                                         MVA  | 
                                                    
                                                         MVA: Used for 3-Phase, SLG, or LL faults  | 
                                                    
                                                        
  | 
                                                
| kA | 
                                                         kA: Used for 3-Phase, SLG, or LL faults  | 
                                                    
                                                        
  | 
                                                
| Ohms | 
                                                        
  | 
                                                    
                                                        
  | 
                                                
| Zpu | 
                                                        
  | 
                                                    
                                                        
  | 
                                                
DC Utility Specifications Tab
                                                
                                            
Figure 3: DC Utility Specifications
| Option | Description | 
|---|---|
| 
                                                         kV  | 
                                                    
                                                         DC Utility operating kV. If this value is different than the bus base kV, then the controlled voltage is scaled appropriately.  | 
                                                
| 
                                                         Fault Duty  | 
                                                    
                                                         Expected fault value (in amperes) or the Thevenin equivalent resistance (in ohms) at the DC utility connection point.  |