DC Effects in Harmonics
In harmonics, expect the following behavior from DC components:
- A Rectifier provides a harmonic injection on its input or load side.
- An Inverter, if specified as Harmonic, is a harmonic source injection on its output with NO SINK (the source to reference bus admittance is not built into the network).
- An Inverter, if specified as Linear is a SINK with its source admittance added to the network on the output of the Inverter.
- No harmonics are simulated on any portion of a DC network.
