UPS - Harmonics Tab

Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.

Figure 1: Harmonics Tab

Option Descriptions
Option Description

Load Type

The default is Linear, indicating the equipment does not produce harmonics. Choosing Harmonic makes the item an harmonic source and makes other fields in this tab available to edit.

Note: For an adjustable frequency drive (AFD), the Load Type is always Harmonic.
For motors, the Load Type is Harmonic if the With Adjustable Frequency Drive (AFD) check box is selected on the Specifications tab of the motor; otherwise, it is always Linear.

Fundamental Amps

Use to set the fundamental amps. The options are as follows:

  • Equipment Rating sets Fundm Amps to the equipment rating of the item described in the Specifications tab. 
  • User Specified activates the Fundm Amps field, enabling you to specify a value. 

To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box.

Harmonic Spreadsheet

Use the spreadsheet to enter the harmonic spectrum produced by this item. You can enter up to 30 different harmonics in each equipment item. In the spreadsheet, enter the Harmonic Number (such as 5 for the 5th harmonic), the Harmonic Current in percent of the Fundamental Amps, and the Current Angle. By indicating the current angle, you can simulate transformer phase shift effects on rectifiers so appropriate canceling can take place. The harmonic may be integer or non-integer.

Library Load

Common harmonic spectra may be entered from the device library. For instructions on how to enter your own spectra information, see Harmonics. After selecting a particular device library spectrum from the Mfr and Type lists, click Import, and that spectrum is entered into the harmonic spreadsheet.

Resistance Factor

EasyPower offers two methods for calculating RH:

  • Resistance varying with a power of the harmonic (R-EXP):
  • RH = RFund * H R-EXP

  • Resistance varying with a percent eddy current factor (%ECF):
  • RH = RFund * (1+ECF*H2)/(1+ECF)

EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.

Typical Resistance Correction Factors

  R-EXP %ECF

Transformer

0.5-1.0

1.0-3.0

Utility

0.0-0.8

    -

Generator

0.3-0.6

    -

Line/Cable

0.5

    -

Reactor

0.5-1.0

0.8-3.0

Motor

0.2-0.4

    -

More Information