IEEE 1584-2018 Range of Model
EasyPower displays an "Out of IEEE 1584-2018 Range" on the Arc Flash Hazard report when parameters are outside of the empirically derived model. Refer to the standard for more information.
|
Parameter |
Range |
|
|---|---|---|
| Voltage | 208 to 15,000 V | |
| Frequency | 50Hz or 60 Hz | |
| Bolted Fault Current |
|
|
| Electrode Gap |
|
|
|
Working Distance |
Greater than or equal to 12 in. (304.8 mm) |
|
|
Fault Clearing Time |
No maximum considered. |
|
|
Enclosure Height |
Less than or equal to 49 in. (1244.6 mm). |
|
|
Enclosure Width |
Less than or equal to 49 in. (1244.6 mm). Greater than four times the gap between electrodes. |
|
|
Enclosure Depth |
No maximum considered. |
|
|
Electrode Configuration |
Electrodes in Enclosures:
Electrodes in Open Air:
Electrode configurations are only applicable to the IEEE 1584-2018 standard. |
|