Shifting Curves by Modifying
You can also shift curves by a percentage you specify. This is done to coordinate devices in parallel paths with an upstream or downstream device. For example, if there were 2 parallel cables with one limiter each of 100A rating the effective total would be 200A. You can shift the 100A fuse curve by 200%. You can also shift fuse curves along the time axis to account for the pre-loading of fuses.
Figure 1: Modify Curve Shift
The following user-specified curve shifting methods are available:
- Left/Right: You can shift the curve along the current axis by the specified percent.
- Up/Down: Shift along the time axis.