Cable - Harmonics Tab
Note: Not applicable to DC cables.
Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.
Figure 1: Harmonics Tab
| Option | Description | |||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Resistance Factor |
EasyPower offers two methods for calculating RH:
RH = RFund * H R-EXP RH = RFund * (1+ECF*H2)/(1+ECF) EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.
|
|||||||||||||||||||||
|
Fundamental Amps |
Use to set the fundamental amps. The options are as follows:
To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box. |
More Information
- Cable Data
- Database Dialog Box Toolbar
- Cable - Connection Information
- Cable - Specifications 1 Tab
- Cable - Specifications 2 Tab
- Cable - Ground Wire Tab
- Cable - Neutral Wire Tab (AC only)
- Cable - Reliability Tab
- Cable - Comments Tab
- Cable - Hyperlinks Tab
- Cable - Collected Data Tab
- Cable - Media Gallery Tab
- Cable - Appearance Tab