UPS - Specifications Tab
Figure 1: Specifications Tab
Figure 2: UPS Short Circuit Output Settings for IEC
| Option | Description |
|---|---|
|
UPS kVA |
kVA rating of the UPS. |
|
X/R |
X/R ratio used for short circuit calculations at the output. |
| Short Circuit Output | |
|
½ Cycle / Initial |
The value is entered as a multiple of the kVA rating. Example: A 500kVA/0.48kV UPS has a momentary short circuit contribution of 3000Amps. The short circuit capability in multiples of kVA rating is 4.988 (~5.0). [ multiple = sqrt(3)*3kA*0.48kV/500kVA.] |
|
Interrupting / Breaking |
|
|
30 Cycle / Steady State |
|