Insert SC Tick Marks

To insert user-defined short circuit tick marks on the TCC plot, on the TCC tab, click  Insert SC Tick Mark.

The Insert SC Tick Mark dialog box (ANSI) is shown.

Figure 1: Insert SC Tick Mark Dialog Box (ANSI)

The Insert SC Tick Mark dialog box (IEC) is shown.

Figure 2: Insert SC Tick Mark Dialog Box (IEC)

Option Descriptions

Option

Description

Current

You can select the appearance of the symbol that represents the short circuit current type.

  • A Symmetrical current appears as an arrow with unfilled head.
  • An Asymmetrical current appears as an arrow with solidly filled head as shown in the figure below.

These are default settings and can be edited by formatting tick marks. You can also save the format as new default tick marks.

An asymmetrical tick mark is shown on the left with a solid arrow head; the symmetrical arrow on the right has a hollow head.

Fault

Selection of fault type affects the time coordinates of the tick mark.

  • The choices for ANSI are Momentary for half cycle, Interrupting for 5 cycles, and 30-cycle.
  • The choices for IEC are Initial, Breaking, and Steady State.

The short circuit tick mark may be dragged vertically within a limited distance.

Short Circuit Current

Enter the short circuit current value in kilo amps The tick mark is placed on the TCC plot at the specified current value times the ratio of short circuit reference voltage to TCC plot reference voltage.

Reference Voltage Enter the reference voltage at the short circuit point in kilo volts. The tick mark is placed on the TCC plot at the specified current value times the ratio of short circuit reference voltage to the TCC Scale reference voltage.

More Information