Notes on Power Factor

Real and Reactive Power Factor (PF and RF)

The Real and Reactive Power Factor of an AC electrical power system provide a ratio of real and reactive power flowing toward a load with respect to the apparent power in the circuit. In EasyPower, the Real Power Factor can be defined between the values of 1 and (-1), where, a negative value represents a leading power factor and a positive value represents a lagging power factor. This can be understood in more depth by applying the reference angle between voltage and current to find the reactive factor (RF) to find the total VAr (VoltAmps-reactive) in the same circuit.

Where a reference angle is defined as: θ REF= θ voltage - θ current

Power Factor: PF= cos⁡ θREF

Reactive Factor: RF= sin⁡ θREF

Therefore, we can see that when we have a negative θREF then the RF is also negative.

So, we may conclude that this implies;

- θ REF→ - kVAr

+ θ REF→ + kVAr

Thus, when entering equipment information in EasyPower for kVA & PF:

- PF → leading PF

+ PF → lagging PF

More Information

Database Technical Reference  
     

www.easypower.com

EasyPower, LLC

7730 SW Mohawk St.

Tualatin, OR 97062

(503)655-5059

techsupport@easypower.com

feedback@easypower.com

EasyPower knowledge base

EasyPower Version 9.8

Copyright © 2017 EasyPower, LLC. All Rights Reserved.

Help was last updated on 7/10/2017