Example 3: Photovoltaic System

This section provides an example of a photovoltaic system. To view the example and perform the tasks, open the Photovoltaic.dez that is available in the Sample directory.

Figure 1: Photovoltaic Example

  1. Click Power Flow, and then click Solve. The power flow results are displayed on the one-line.
  2. Select Short Circuit to open the short circuit focus.

  3. Click Momentary if it is not already selected, and then click Fault Bus(es).
  4. View the momentary currents on the one-line. At every bus compare the fault current contribution from each branch. For instance, PVC-1 bus has a small fault current supplied from the photovoltaic PVC-1, and a larger current from the bus COMBINER-1.
  5. Click Arc Flash to view the arc flash hazard results.
  6. Click Short Circuit Options and select the Arc Flash Hazard tab. Note the options circled below.
  7. Figure 2: Arc Flash Hazard Options

  8. Change the option Calculate Arc Flash Using to Momentary and view results at bus PVC-1. The result is not calculated because there is no trip device modeled between the faulted bus and the photovoltaic source PVC-1.

More Information

DC Models and Analysis Example 1: Sample DC System
Tips on Creating DC Systems Example 2: DC Link Inverter with a Battery Bank (UPS)
DC in EasyPower  
     

www.easypower.com

EasyPower, LLC

7730 SW Mohawk St.

Tualatin, OR 97062

(503)655-5059

techsupport@easypower.com

feedback@easypower.com

EasyPower knowledge base

EasyPower Version 9.8

Copyright © 2017 EasyPower, LLC. All Rights Reserved.

Help was last updated on 7/10/2017