Mensajes de Error de Datos

Descripción (Description) - En algunos modelos, los datos de entrada se comprueban para el funcionamiento del modelo correcto a la inicialización. Esto es especialmente cierto cuando modelos particulares crearán división numérica por cero o una condición de retroalimentación positiva si los constantes caen dentro de un rango específico.

Soluciona - Si aparecen estos errores, debe solucionarlos para realizar una simulación. Cambie los valores para que no activan el error, entonces representan valores que proporcionan una respuesta del modelo correcto.

"Steam Turbine Gov1 T1 is <= zero."

"Steam Turbine Gov1 T3 is <= zero."

"Steam Turbine Gov1 R is <= zero."

"Diesel Gov1 T1 is <= zero."

"Diesel Gov1 T2 is <= zero."

"Diesel Gov1 T5 is <= zero."

"Diesel Gov1 T6 is <= zero."

"Gas Turbine Gov1 R is <= zero."

"Gas Turbine Gov1 T1 is <= zero."

"Gas Turbine Gov1 T2 is <= zero."

"Gas Turbine Gov1 T3 is <= zero."

"Woodward Steam PID1 TB is <= zero."

"Woodward Steam PID1 TC is <= zero."

"Woodward Steam PID1 TD is <= zero."

"Simple Exciter K is <= zero."

"Simple Exciter TE is <= zero."

"Simple Exciter TB is <= zero."

"Simple Exciter EMax is <= EMin."

"IEEET1 Exciter KA is <= zero."

"IEEET1 Exciter TF is <= zero."

"IEEET1 Exciter TR is <= zero."

"IEEET1 Exciter TA is <= zero."

"IEEET1 Exciter TE is <= zero."

"IEEET1 Exciter E2 is < E1."

"IEEET1 Exciter S(E2) is <= S(E1)."

"IEEET1 Exciter VRMax is <= VRMin."

"IEEE AC6A KA is <= zero."

"IEEE AC6A TA is <= zero."

"IEEE AC6A TB is <= zero."

"IEEE AC6A TH  is <= zero."

"IEEE AC6A TR is <= zero."

"IEEE AC6A TE is <= zero."

"IEEE AC6A E2 is <= E1."

"IEEE AC6A S(E2) is <= S(E1)."

"IEEE AC6A VRMax is <= VRMin."

"IEEE AC6A VAMax is <= VAMin."

"IEEE AC8B TR is <= zero."

"IEEE AC8B TDR is <= zero."

"IEEE AC8B TA is <= zero."

"IEEE AC8B TE is <= zero."

"IEEE AC8B TH is <= zero."

"IEEE AC8B S(E2) is <= S(E1)."

"IEEE AC8B VRMax is <= VRMin."

"IEEE AC8B VEMax is <= VEMin."

"Round Rotor Gen E2 is <= zero."

"Round Rotor Gen S(E2) is <= zero."

"Round Rotor Gen has improper saturation constants - 1."

"Round Rotor Gen has improper saturation constants - 2."

"Round Rotor Gen E2 is <= E1."

"Round Rotor Gen S(E2) is <= S(E1)"

"Round Rotor Gen X''d is <= Xl."

"Round Rotor Gen X''q is <= Xl."

"Round Rotor Gen X'd is <= Xl."

"Round Rotor Gen X'q is <= Xl."

"Round Rotor Gen Xd is <= X'd."

"Round Rotor Gen Xq is <= X'q."

"Round Rotor Gen T'do is <= T''do."

"Round Rotor Gen T'qo is <= T''qo."

"Round Rotor Gen Xd is <= Xl."

"Round Rotor Gen Xq is <= Xl."

"Round Rotor Gen T'do is <= zero."

"Round Rotor Gen T''do is <= zero."

"Round Rotor Gen T'qo is <= zero."

"Round Rotor Gen T''qo is <= zero."

"Round Rotor Gen H is <= zero."

"Round Rotor Gen Rated kV is <= zero."

"Round Rotor Gen Bus kV is <= zero."

"Round Rotor Gen MVA is <= zero."

"Salient Pole Gen E2 is <= zero."

"Salient Pole Gen S(E2) is <= zero."

"Salient Pole Gen has improper saturation constants - 1."

"Salient Pole Gen has improper saturation constants - 2."

"Salient Pole Gen E2 is <= E1."

"Salient Pole Gen S(E2) is <= S(E1)."

"Salient Pole Gen X''d is <= Xl."

"Salient Pole Gen X'd is <= Xl."

"Salient Pole Gen Xd is <= X'd."

"Salient Pole Gen X'd is <= X''d."

"Salient Pole Gen Xq is <= X''q."

"Salient Pole Gen T'do is <= T''do."

"Salient Pole Gen T'do is <= zero."

"Salient Pole Gen T''do is <= zero."

"Salient Pole Gen T''qo is <= zero."

"Salient Pole Gen H is <= zero."

"Salient Pole Gen Rated kV is <= zero."

"Salient Pole Gen Bus kV is <= zero."

"Salient Pole Gen MVA is <= zero."

Más Información