Tips on Creating DC Systems
The following are recommendations when creating DC one-lines.
- Always use an inverter or a rectifier to interconnect AC and DC systems.
- Choose the appropriate voltage for AC or DC buses. For rectifiers and inverters without voltage control, the typical ratio is:
- AC equipment cannot be connected to DC equipment.
- While placing breakers on inverters or rectifiers, connect the AC breaker on the AC side and DC breaker on the DC side.
- Make sure breakers and fuses are "in-line" with the branch equipment. If the breaker is "in-line" with the equipment, then moving the breaker left or right on the one-line will move the equipment as well. See below.
- DC switches are currently not available in the equipment palette. For a DC switch, use a DC breaker instead.
VDC = 1.35 * VAC
AC voltage is rms value whereas the DC is average. Failure to set voltages correctly could result in an incorrect power flow solution.
Figure 1: Breakers Shown In and Out of Line
More Information
| DC Models and Analysis | Example 3: Photovoltaic System |
| Example 1: Sample DC System | DC in EasyPower |
| Example 2: DC Link Inverter with a Battery Bank (UPS) |
|