A filter is a passive tuned circuit that presents a low impedance “sink” to currents at a given frequency or frequencies. Filter on the equipment palette toolbar inserts a filter in the one-line diagram. The application of harmonic filters can cause the creation of parallel resonance below the filter tuning point (single tuned notch). The filter must be designed to minimize the impact of this resonant point.
This dialog box includes the following areas and tabs:
Figure 1: Filter Data Dialog Box
ID Name: Uniquely identifies the filter. This ID name is sometimes referred to as the filter name, and can be up to 12 characters long. The names default to FL-1, FL-2, FL-3, and so on as you enter new filters on the one-line diagram, but these names can be changed if needed.
To Bus: The bus to which the filter connects, which must already exist on the one-line. For your reference, the To Bus base kV is displayed next to the bus name.
Type: You can select from four different types of filters. When you choose the type of filter, EasyPower makes unavailable any filter data fields that do not apply to the selected filter.
Figure 2: Filter Types
Resistor: Resistance of resistor of the filter in ohms.
Inductor: Real and imaginary impedances (ohmic resistance and inductive reactance) at system frequency in ohms.
Capacitor Bank (1 and 2): The reactive power of capacitors for the system frequency in MVARs at the voltage level specified in kilovolts.
Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.
EasyPower offers two methods for calculating RH:
RH = RFund * H R-EXP
RH = RFund * (1+ECF*H2)/(1+ECF)
EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.
R-EXP | %ECF | |
---|---|---|
Transformer |
0.5-1.0 |
1.0-3.0 |
Utility |
0.0-0.8 |
- |
Generator |
0.3-0.6 |
- |
Line/Cable |
0.5 |
- |
Reactor |
0.5-1.0 |
0.8-3.0 |
Motor |
0.2-0.4 |
- |
Use to set the fundamental amps. The options are as follows:
To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box.
This tab is read-only and appears only if you have imported data from an SKM Data Format file. See Importing an SKM Format File for more information.
See Comments for information.
See Hyperlinks for information.