This dialog box includes the following areas and tabs:
Figure 1: Zigzag Data Dialog Box
| Option | Description |
|---|---|
| Voltage Rating (kV) | Transformer nameplate rated kV. |
| Impedance (Ohms) | Transformer nameplate impedance in ohms. This is the impedance between each line terminal and neutral. |
| R | Transformer neutral ground resistance in ohms. |
| jX | Transformer neutral ground reactance in ohms. |
Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.
Figure 2: Harmonics Tab
| Option | Description | |||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Resistance Factor |
EasyPower offers two methods for calculating RH:
RH = RFund * H R-EXP RH = RFund * (1+ECF*H2)/(1+ECF) EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.
|
|||||||||||||||||||||
| Fundamental Amps |
Use to set the fundamental amps. The options are as follows:
To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box. |
See Location for more information.
This tab is read-only and appears only if you have imported data from an SKM Data Format file. See Importing an SKM Format File for more information.
See Comments for information.
See Hyperlinks for information.