Motor - Motor Starting Tab
Option | Description |
---|---|
Motor kW or Motor HP |
The required input or rated power of the motor. |
kVA/kW or kVA/HP |
Represents the efficiency of the motor. It is a conversion factor for delivered power and the required input power. |
Locked Rotor Mult |
Equal to the inverse of the subtransient reactance (also known as X"dv) and provides the value at which the full load amp rating of the motor is multiplied under short circuit conditions. |
Starting Power Factor |
The momentary power factor during the start of the motor. While the motor is under starting conditions, the reactive power is higher than the real power as a result of the starting power factor. |
Auto-calculate |
Select to have EasyPower determine motor starting values. EasyPower references IEEE standards for the calculations. |
More Information
- Motor Data
- Database Dialog Box Toolbar
- Motor - Connection Information
- Motor - Specifications Tab
- Motor - Short Circuit Tab
- Motor - TCC Tab
- Motor - Power Flow Tab
- Motor - Harmonics Tab
- Motor - Stability Tab
- Motor - Reliability Tab
- Motor - Location Tab
- Motor - Comments Tab
- Motor - Hyperlinks Tab
- Motor - Collected Data Tab
- Motor - Media Gallery Tab