Three Winding Transformer - Harmonics Tab
Figure 1: Harmonics Tab
Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.
Resistance Factor
EasyPower offers two methods for calculating RH:
- Resistance varying with a power of the harmonic (R-EXP):
- Resistance varying with a percent eddy current factor (%ECF):
RH = RFund * H R-EXP
RH = RFund * (1+ECF*H2)/(1+ECF)
EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.
| R-EXP | %ECF | |
|---|---|---|
|
Transformer |
0.5-1.0 |
1.0-3.0 |
|
Utility |
0.0-0.8 |
- |
|
Generator |
0.3-0.6 |
- |
|
Line/Cable |
0.5 |
- |
|
Reactor |
0.5-1.0 |
0.8-3.0 |
|
Motor |
0.2-0.4 |
- |
Fundamental Amps
Use to set the fundamental amps. The options are as follows:
- Equipment Rating sets Fundm Amps to the equipment rating of the item described in the Specifications tab.
- User Specified activates the Fundm Amps field, enabling you to specify a value.
To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box.
| Option | Description |
|---|---|
|
Pri Fundm Amps |
Calculated rated amps on the primary side. |
|
Sec Fundm Amps |
Calculated rated amps on the secondary side. |
|
Ter Fundm Amps |
Calculated rated amps on the tertiary side. |
|
Rated eddy-current loss, Pec-r |
Eddy-current loss under rated conditions expressed as a percentage of rated I2R loss. |
More Information
- Three Winding Transformer Data
- Database Dialog Box Toolbar
- Three Winding Transformer - Connection Information
- Three Winding Transformer - Specifications Tab
- Three Winding Transformer - Impedance Tab
- Three Winding Transformer - TCC Tab
- Three Winding Transformer - LTC (Load Tap Changer) Tab
- Three Winding Transformer - Reliability Tab
- Three Winding Transformer - Location Tab
- Three Winding Transformer - Comments Tab
- Three Winding Transformer - Hyperlinks Tab
- Three Winding Transformer - Collected Data Tab
- Three Winding Transformer - Media Gallery Tab