Three Winding Transformer - Specifications Tab
Figure 1: Specifications Tab
| Option | Description |
|---|---|
|
Type |
Type of transformer (oil, gas, dry, silicone, or vapor). This field is used to determine the rating capacity of the transformer for the power flow overload solution. |
|
Class |
Type of cooling used by the transformer. Various combinations of forced air, water and forced oil are available. This field is used to determine the rating capacity of the transformer for the power flow overload solution. |
|
Temp |
ANSI temperature rating of the transformer. Various combinations can be chosen and are dependent upon the type of transformer. Dual ratings such as 55/65 increase the overload capability of the transformer by 12 percent. |
|
Form |
Either core or shell type transformers can be selected. If Core is selected, the Z0% value on the Impedance tab is set to 0.85 of Z%. If Shell is selected, Z0% is equal to Z%. |
|
Winding Information |
|
|
Rated kV |
Rated kV of a winding. The rated kV can be different than the base kV or the tap kV. EasyPower automatically adjusts the model to account for different taps, turns ratio and bases you choose. |
|
Tap kV / Tap% |
Tap kV of a winding. You can also specify the tap kV in terms of percentage of the rated value. If the actual tap kV is not known, enter the rated kV. Load tap changer control can be used to determine final tap settings if desired. EasyPower automatically adjusts the model to account for different taps, turns ratio and bases you select. |
|
MVA/kVA |
Self cooled rating of the transformer. Use to select the unit in MVA or kVA. |
|
MVA OL |
The overload rating is based on the temperature and class ratings. It is filled in using the Calculate button or you can type in a different rating. |
More Information
- Three Winding Transformer Data
- Database Dialog Box Toolbar
- Three Winding Transformer - Connection Information
- Three Winding Transformer - Impedance Tab
- Three Winding Transformer - TCC Tab
- Three Winding Transformer - LTC (Load Tap Changer) Tab
- Three Winding Transformer - Harmonics Tab
- Three Winding Transformer - Reliability Tab
- Three Winding Transformer - Location Tab
- Three Winding Transformer - Comments Tab
- Three Winding Transformer - Hyperlinks Tab
- Three Winding Transformer - Collected Data Tab
- Three Winding Transformer - Media Gallery Tab