Inverter Data

This dialog box includes the following areas and tabs:

See Common Tabs for information on the Location, Comments, Hyperlinks, or Collected Data tabs.

See also Notes on Inverter Model.

Figure 1: Inverter Data Dialog Box

Connection Information

Option Description
ID Name

Uniquely identifies the equipment item. The program automatically assigns a name, but you can change it, if needed. The name can be up to 16 characters long.

For inverters, the program automatically assigns the names INV-1, INV-2, INV-3, and so on.

Input Bus The DC bus to which the inverter connects, which must already exist on the one-line. For your reference, the Input Bus base kV is displayed next to the bus name.
Output Bus

The AC bus to which the inverter connects, which must already exist on the one-line. For your reference, the base kV is displayed next to the bus name.

Phase

The phase of the item. Currently, this is for reference only.

Specifications Tab

Option Description
kVA Rated output kVA of the inverter.
X/R X/R ratio of the inverter short circuit contribution as seen from the load side.
IGBT / Thyristor Type of inverter. This affects power flow simulation methods. If IGBT, there are three control modes possible. For Thyristor, the output real and reactive power conditions are simulated using Kimbark’s equations.
Fault x FLA Maximum fault current expected on the load side in multiples of the full load amps (FLA) rating.
Fault Time Duration the inverter can supply the fault current. The time can be specified in cycles or seconds.

Power Flow Tab

Figure 2: Power Flow tab of the Inverter Dialog Box

Option Description
Model

Describes the way the output of the inverter is controlled for IGBT type. The options are:

  • Stand Alone: The inverter will supply any amount of required load, just like an AC grid Swing Bus. The specified voltage magnitude (Ctrl kV PU) and angle (Ctrl Angle) will be maintained. You should carefully check the capability (limits) of the inverter.
  • Voltage Controlled: This model supplies the specified amount of kW to connected system, keeping the voltage magnitude at specified value (Ctrl kV PU) on the load side bus. There must be a Stand Alone system present when an inverter is operating in Voltage Controlled mode. Specify the kVAR Min and kVAR Max limits for the inverter.
  • Const PQ Output: This model supplies the specified amount of kW and kVAR to connected system. There must be a Stand Alone system present when an inverter is operating in Const PQ Output mode. Specify the kVAR Min and kVAR Max limits for the inverter.
Ctrl kV PU The per unit magnitude of Inverter output voltage. This is maintained at the specified value for a Stand Alone model, and is maintained at the specified value while within var limits for a Voltage Controlled model.
Ctrl Angle The angle in degrees of the controlled output voltage for Stand Alone model.
Eff Efficiency of the inverter. This is the ratio between output and input power in percent.
kW Specified controlled output active power in kW for Voltage Controlled and Const PQ Output models.
kVAR Specified controlled output reactive power in kVAR for Const PQ Output models.
kVAR Min Minimum kVAR capability of the inverter in voltage controlled mode.
kVAR Max Maximum kVAR capability of the inverter in voltage controlled mode.
Min Voltage Threshold

For an IGBT inverter only, if the DC voltage on the input to the inverter drops below this value, then the inverter begins stepping its specified kW loading down until the input voltage rises above Min Voltage Threshold.

Note: The power flow will not solve when loading on photovoltaics causes them to experience a severe terminal under-voltage. Therefore, this special control was added so that inverters fed by photovoltaics reduce load when voltage drops below VMP so that photovoltaics are required to supply less power, thus helping the DC voltage on the photovoltaics increase into a range where a power flow solution can be reached.

Gamma Min Minimum inverter margin angle in degrees for thyristor type inverter.
Gamma Max Maximum inverter margin angle in degrees for thyristor type inverter.
Commutation Impedance

Commutation impedance used to calculate the power flow using Kimbark’s equations with Thyristor type. The inverter must feed a dedicated transformer that matches these same values one-for-one.

  • Z1: Commutation impedance in percent on kVA base specified below. This must correspond to the downstream transformer.
  • X/R: X/R ratio of the commutation impedance. This must correspond to the downstream transformer.
  • kVA: kVA rating base for Z1. This must correspond to the downstream transformer.

Harmonics Tab

Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.

Figure 3: Harmonics Tab

Option Description
Load Type

The default is Linear, indicating the equipment does not produce harmonics. Choosing Harmonic makes the item an harmonic source and makes other fields in this tab available to edit.

Note: For an adjustable frequency drive (AFD), the Load Type is always Harmonic.
For motors, the Load Type is Harmonic if the With Adjustable Frequency Drive (AFD) check box is selected on the Specifications tab of the motor; otherwise, it is always Linear.

Fundamental Amps

Use to set the fundamental amps. The options are as follows:

  • Equipment Rating sets Fundm Amps to the equipment rating of the item described in the Specifications tab. 
  • User Specified activates the Fundm Amps field, enabling you to specify a value. 

To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box.

Harmonic Spreadsheet

Use the spreadsheet to enter the harmonic spectrum produced by this item. You can enter up to 30 different harmonics in each equipment item. In the spreadsheet, enter the Harmonic Number (such as 5 for the 5th harmonic), the Harmonic Current in percent of the Fundamental Amps, and the Current Angle. By indicating the current angle, you can simulate transformer phase shift effects on rectifiers so appropriate canceling can take place. The harmonic may be integer or non-integer.

Library Load

Common harmonic spectra may be entered from the device library. For instructions on how to enter your own spectra information, see Harmonics with Spectrum™. After selecting a particular device library spectrum from the Mfr and Type lists, click Import, and that spectrum is entered into the harmonic spreadsheet.

Resistance Factor

EasyPower offers two methods for calculating RH:

  • Resistance varying with a power of the harmonic (R-EXP):
  • RH = RFund * H R-EXP

  • Resistance varying with a percent eddy current factor (%ECF):
  • RH = RFund * (1+ECF*H2)/(1+ECF)

EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.

Typical Resistance Correction Factors

  R-EXP %ECF

Transformer

0.5-1.0

1.0-3.0

Utility

0.0-0.8

    -

Generator

0.3-0.6

    -

Line/Cable

0.5

    -

Reactor

0.5-1.0

0.8-3.0

Motor

0.2-0.4

    -

Stability Tab

Figure 4: Stability Tab

Generator Model

Option Description
Enable Generator Model Select the check box to enter stability information.
Mfr Provides a list of manufacturers available in the device library. If the desired manufacturer is not listed in the device library, you can add it to the library.
Type Equipment types available from the selected manufacturer. If the desired type is not listed, you can add it to the library.
Model Equipment models available from the selected equipment type. If the desired model is not listed, you can add it to the library.
Lib Populates the table with equipment data from the library. See EasyPower Device Library for more information.

Exciter Model

Option Description
Enable Exciter Model Select the check box to enter stability information.
Mfr Provides a list of manufacturers available in the device library. If the desired manufacturer is not listed in the device library, you can add it to the library.
Type Equipment types available from the selected manufacturer. If the desired type is not listed, you can add it to the library.
Model Equipment models available from the selected equipment type. If the desired model is not listed, you can add it to the library.
Lib Populates the table with equipment data from the library. See EasyPower Device Library for more information.

Other Tabs

See Common Tabs for information on the Location, Comments, Hyperlinks, or Collected Data tabs.

More Information

Database Technical Reference Common Tabs
Notes on Inverter Model  
Media Gallery  
     

www.easypower.com

EasyPower LLC

7730 SW Mohawk St.

Tualatin, OR 97062

(503)655-5059

techsupport@easypower.com

feedback@easypower.com

EasyPower knowledge base

EasyPower Version 10.2

Copyright © 2019 EasyPower LLC. All Rights Reserved.

Help was last updated on 3/22/2019