Control Tab

To set short circuit options, from the Short Circuit focus, click SC Options. You can also access the options from within the Database Edit focus by selecting Tools > Options > Analysis Options > Short Circuit.

On the Control tab, specify the options you want for controlling the behavior of a short circuit study.

Figure 1: Control Tab of the Short Circuit Options Dialog Box

Option Descriptions
Option Description

Fault Type for 3PH buses

For 3-phase faults, there are four different types of faults available during a short circuit analysis. The default is 3 Phase which is generally used to determine the highest available currents for equipment duty comparisons, and relaying. The other types, Line to Ground, Double Line to Ground, and Line to Line are generally used for specialized relaying applications or system troubleshooting. You can specify the phases to fault for each fault type. During short circuit analysis, the program automatically changes the display phases if the phases selected appear on the one-line do not match these fault values.

Note: Your phase descriptions may be different than described here if they have been customized in Tools > Options > Terminology.

Fault Type for 1PH buses

For single-phase faults, there are three different types of faults available during a short circuit analysis. You can specify the phases to fault for each fault type. The options are as follows:

  • 1PH-3W: For single-phase-3-wire faults, the options are line-to-neutral (LN) or line-to-line (LL).
  • 1PH-2W Line to Neutral: For single-phase-2-wire line-to-neutral faults, the option is line-to-neutral (LN). This is for reference and cannot be changed.
  • 1PH-2W Line to Line: For single-phase-2-wire line-to-line faults, the options are double-line-to-ground (DLG ) or line-to-line (LL).

X/R Calculation Type

Short circuit calculations are based on one of three methods:

  • The ANSI Standard method uses a separate R network for the interrupting duty (2-5 cycle) network to determine a conservative Z/R ratio. This ratio is then used as the Thevenin equivalent fault point X/R ratio for determining the appropriate breaker contact parting time multipliers and NACD ratios. Current and voltage calculations are based on a complex (R+jX) network reduction. Both the momentary (1/2 Cycle) and 30 cycle calculations use a complex network reduction for all voltage, current, and X/R ratio calculations.
  • The Standard Complex(non-ANSI) calculation uses a complex network reduction for all momentary, interrupting duty, and 30 cycle voltage, current, and X/R ratio calculations.
  • The Characteristic Current Method (CCM) calculates the DC component of each branch based on phase angle of the current flowing in it and then sums the DC component in each branch contributing to the fault current. The ratio of the total DC to the total AC is used to determine the equivalent X/R at fault point. Branch current flows having different current phase angles (X/R ratios) will have the current peak at slightly different times before the first-half cycle. To simplify calculations, the DC component is taken at 0.5-cycle for all branches using the expression in equation below.
  • IDC = Ö2 IAC RMS SYM exp (-p /|X/R|)

    After each DC component is determined and totaled, the equivalent X/R ratio is found from the equation below.

    Equivalent X/R = -p/ ln (S IDC / S IAC RMS SYM / Ö2)

    Reference:
    Parise G., A new approach to calculate the decaying AC contributions to short-circuit: the ‘characteristic’ currents method; IEEE Transactions on Industry Applications, Vol. 31, No. 1, January/February 1995.

"Fault All" Filters

Enables you to specify a specific bus Area, Zone, and kV Range that to fault and report when you fault multiple or all buses. This type of analysis is useful when you are interested in studying only a specific region and do not need all of the output associated with a full system analysis. This method is common for old-style text programs. In EasyPower, it is just as simple to select the buses you wish to fault from the one-line fault buses. Only the selected buses are faulted.

Driving Point Voltage (pu)

System fault point voltage in per-unit. This value defaults to 1.0 per-unit.

Include Single Phase Buses

Selects whether single-phase buses are included when bus faults are performed. By default, this option is selected.

Equipment Duty Threshold

Sets the lower limit for flagging breaker violations in SmartDuty™. If the threshold is set to -10 percent, SmartDuty™ will flag all equipment which has short circuit duties within 10 percent of their maximum rating (greater than 90% of their rating).

Note: The ability to automatically check equipment duties during analysis is only available if you have purchased the SmartDuty™ option to EasyPower.

For example, a GE AM-13.8-500 air blast breaker has a momentary and interrupting duty rating of 19.56/37 kA at 13.8 kV. SmartDuty™ provides a warning flag if the current exceeds 17.6/33.3 kA in either the momentary or interrupting rating. If the current exceeds 19.56/37 kA, a violation is flagged.

Note: You must click  Equipment Duty from the Short Circuit focus for this field to have any effect on the one-line result output. 
For this field to have any effect for text result output, you must select the Create Equipment Duty report check box in the Text Output tab of the Short Circuit Options dialog box.

Voltage Sensitivity Threshold

Sets the lower limit setting for flagging voltage violations. If the threshold is set to -30 percent, bus voltages lower than 30 percent (70 percent voltage) of the bus' base kV is flagged. This enables you to quickly check for motor contactor dropout, lighting flicker, and so on.

Note: For this field to have any effect, you must select one or more of the Voltage Sensitivity check boxes in the One-line Output or the Text Output tab of the Short Circuit Options dialog box.

Compare 1PH Device Rating to Device/Bus Current

  • Device: This applies the 1-phase fault type and compares the device ratings with the fault currents through the 1-phase devices (see the options under Fault Type for 1PH buses). This applies to protective devices that appear in the one-line view. Devices within panels and MCCs are compared to the bus current.
  • Bus: This choice applies the types of fault available at the bus. 3-phase buses can have the faults 3-phase, single-line-to-ground, double-line-to-ground, or line-to-line. You can choose the fault type for 3-phase buses from the Short Circuit Options or from the short circuit menu. 1PH-3W buses can have a line-to-ground fault or a line-to-line fault. For 1PH-3W, you can choose the fault type only from within this dialog box.

For more information, see Equipment Duty for Single-Phase Devices.

Default

In the Short Circuit Options Defaults dialog box, you can specify which default short circuit option settings you want to use. This affects the settings in the entire dialog box and is not limited to only the currently selected tab. These default settings are used for all new one-lines.

The options are:

  • Store Current Options as Default Settings: This stores all of the current short circuit options in your equipment defaults file.

  • Reset Current Options to Default Settings: This updates all of the current short circuit options based on those you stored previously in your equipment defaults file.

  • Reset Current Options to Factory Settings: This updates all of the short circuit options to match the defaults that are included in the initial installation of the EasyPower program.

Default settings specified here only affect ANSI settings.

More Information