Panel Data
This dialog box includes the following areas and tabs:
- Database Dialog Box Toolbar
- Connection Information
- Specifications Tab
- Incoming Tab
- Description Tab
- Summary Tab
- Power Flow Tab
- Harmonics Tab
- Arc Flash Hazard Tab
- Accessories Tab
- Change Management Tab
See Common Tabs for information on the Location, Comments, Hyperlinks, or Collected Data tabs.
Figure 1: Panel Data Dialog Box
Connection Information
| Option | Description |
|---|---|
| ID Name |
Uniquely identifies the equipment item. The program automatically assigns a name, but you can change it, if needed. The name can be up to 16 characters long. For panels, the program automatically assigns the names PNL-1, PNL-2, PNL-3, and so on. |
| Base kV |
The base kV of the panel. |
|
Service |
The service for the panel. Select from 3 Phase - 3 Wire, 3 Phase - 4 Wire, 1 Phase - 2 Wire, or 1 Phase - 3 Wire. See Panel Row Behaviors for more information on how the service selection affects the panel rows. Note: To use the Single Phase Panel Schedule Template on the panel, select either of the 1 Phase options. See File-Specific Templates for more information. |
| Upstream Rating | The minimum amp rating of equipment that is upstream from the panel (such as breakers, transformers, or cables). This information is for reference in certain specific configurations of EasyPower and is not generally visible. |
|
Spreadsheet View and Configure |
See Configuring the Spreadsheet View for information about these options. |
| Lock Auto-Sizing | When this check box is selected, this item cannot be automatically sized using SmartDesign™ (the auto-design feature). |
| Tools | Use to enter tool information about the panel. See Edit Tools for more information. |
Specifications Tab
Incoming Tab
Figure 2: Incoming Tab in Panel Data
| Option | Description |
|---|---|
| Incoming Device Type |
You can select the type of incoming protective device type for the panel. The choices available are:
|
| Incoming Branch | You can select the incoming branch equipment such as cables, transformers or busways. All the branches connected to the panel in the one-line are displayed in the list. |
| Incoming Device Settings | Opens the data dialog for the main fuse or main breaker that has been specified as the incoming device type. Refer to Low Voltage Breaker Data or Fused Switch Data for details. |
| Device Information | Information on the selected main breaker or main fuse. |
Description Tab
This is a spreadsheet listing similar to the Device Library. When you place a new panel on the one-line, the first time you open its database dialog and click on the Description tab, EasyPower displays the Panel Schedule Spreadsheet Creation Wizard which enables you to select the number of rows you want. Clear the check box at the bottom of the wizard dialog if you don't want it to appear with each new panel.
Figure 3: Panel Schedule Spreadsheet Creation Wizard Dialog Box
When you click on the Description tab, additional buttons become available on the toolbar. These enable you to perform actions related to the spreadsheet. See Additional MCC and Panel Spreadsheet Options for more information.
Figure 4: Description Tab of Panel Data Dialog Box
| Option | Description |
|---|---|
| Library | The list contains all of the same schedules as the Device Library. To enter a listing other than those contained in the list, create a new page in the panel section of the Device Library. |
| Schedule | This list enables you to specify in which Device Library Schedule your chosen Library Load spreadsheet is located. To enter a listing other than those contained in the list, create a new page in the panel section of the Device Library. |
| Panel Load Units | Select the panel load units, from VA or Amps. |
| View | These options enable you to choose which of the panels you want to view: detailed left, right or both. The choice Simplifiedshows the ABC buses in the middle with the loads on both sides of the spreadsheet. |
Spreadsheet
| Option | Description |
|---|---|
| ECR Type | This is a reference for a type of electrical change request. It is only used in very specific configurations of EasyPower and is otherwise unavailable. |
| Preassigned | Indicates if a change request is pending for this item. It is only used in very specific configurations of EasyPower and is otherwise unavailable. |
| Library Load | This list corresponds directly to the Library Load column in the Device Library. After you have made selections in the Library, Schedule and Library Load fields, all of the following data cells are automatically filled in as soon as you click on another cell. You may also double-click on the cell to enter something different than what is listed. |
| Status | The column is a toggle "On/Off" to indicate if this particular item is currently connected to the panel. Turning any load as “off” is similar to deactivating them in the one-line. |
| Load Type |
You can select from three types of load:
|
| Facility | The facility (building) for the panel row. Facilities are set up on the menu beneath Tools > Options. |
| Location | The location within the facility for the panel row. Locations are set up on the menu beneath Tools > Options. |
| Floor | The floor of the facility where the panel row is located. Floors set up on the menu beneath Tools > Options. |
The rest of the fields correspond directly to those in the Device Library. See EasyPower Device Library for more information.
For additional information on the spreadsheet, see the following topics:
-
For information on how to configure the columns that appear in the spreadsheet view, see Configuring the Spreadsheet View.
-
For information on exporting schedules, see Exporting an MCC or Panel Schedule. The spreadsheets can be exported to metafiles (.WMF) and delimited database text files (.CSV).
- For notes on panel spreadsheets, see Panel Spreadsheet Notes.
- For panel row behavior, including how to insert, move or delete rows, see Panel Row Behaviors.
Summary Tab
The summary tab sums all the connected loads and displays results for total connected, demand, code factor and design. There are two sections in this summary: Panel Load and Including Downstream Load.
Figure 5: Summary tab of Panel Data Dialog Box
| Option | Description |
|---|---|
|
Calculate Downstream Load
|
Calculates the total load on the panel, taking into account the connected load, demand factors, and NEC code factors. |
| Override with User Values | This check box enables you to enter your own data. You can enter measured data or assumed data in the available fields. If this check box is not enabled, then the program calculates all the downstream loads and displays the total. For this feature to work, it is necessary to have a source upstream to the panel. This feature is applicable only to radial distribution systems. Downstream branches with any power source are not accounted for. |
Panel Load
This summarizes the loads fed directly from this panel. It does not include loads fed through downstream sub-panels. These are not user-definable fields. They are updated automatically when you make changes in the spreadsheet of the Description tab. The watts and vars shown in this table do not reflect the downstream load of the sub-panels.
| Option | Description |
|---|---|
|
Connected W (A phase): |
Total of the |
|
Connected VAR (A phase): |
Total of the |
|
Connected W (B phase): |
Total of the |
|
Connected VAR (B phase): |
Total of the |
|
Connected W (C phase): |
Total of the |
|
Connected VAR (C phase): |
Total of the |
|
Demand W (A phase): |
Total of the |
|
Demand VAR (A phase): |
Total of the |
|
Demand W (B phase): |
Total of the |
|
Demand VAR (B phase): |
Total of the |
|
Demand W (C phase): |
Total of the |
|
Demand VAR (C phase): |
Total of the |
| Option | Description |
|---|---|
| Including Downstream Load | Loads connected through downstream sub-panels and buses are summarized in this section. |
Power Flow Tab
Figure 6: Power Flow Tab of Panel Data Dialog Box
SCADA Model
SCADA data is derived from real time, or metered data, and converted to an ASCII format which can be read into EasyPower. SCADA data is read in as a 100% scaling factor load. The load value is multiplied by the user-defined scaling factor. This provides a way to adjust SCADA loads to form new cases.
Harmonics Tab
Use the Harmonics tab to indicate whether this equipment item is introducing harmonics into your power system.
Figure 7: Harmonics Tab
| Option | Description | |||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Load Type |
The default is Linear, indicating the equipment does not produce harmonics. Choosing Harmonic makes the item an harmonic source and makes other fields in this tab available to edit. Note: For an adjustable frequency drive (AFD), the Load Type is always Harmonic. |
|||||||||||||||||||||
| Fundamental Amps |
Use to set the fundamental amps. The options are as follows:
To use fundamental current calculated by power flow, select Calculated from Power Flow in the Summation Fundamental Voltage area of the Harmonics Options > Control dialog box. |
|||||||||||||||||||||
| Harmonic Spreadsheet |
Use the spreadsheet to enter the harmonic spectrum produced by this item. You can enter up to 30 different harmonics in each equipment item. In the spreadsheet, enter the Harmonic Number (such as 5 for the 5th harmonic), the Harmonic Current in percent of the Fundamental Amps, and the Current Angle. By indicating the current angle, you can simulate transformer phase shift effects on rectifiers so appropriate canceling can take place. The harmonic may be integer or non-integer. |
|||||||||||||||||||||
| Library Load |
Common harmonic spectra may be entered from the device library. For instructions on how to enter your own spectra information, see Harmonics with Spectrum™. After selecting a particular device library spectrum from the Mfr and Type lists, click Import, and that spectrum is entered into the harmonic spreadsheet. |
|||||||||||||||||||||
| Resistance Factor |
EasyPower offers two methods for calculating RH:
RH = RFund * H R-EXP RH = RFund * (1+ECF*H2)/(1+ECF) EasyPower defaults all skin effect correction to R-EXP and a value of 0.5.
|
Arc Flash Hazard Tab
EasyPower calculates arc flash risk assessment results using the options set on the Arc Flash Hazard tab. The results are calculated for automatic transfer switches, buses, tool points of connection, MCCs, and panels.
Figure 8: Arc Flash Hazard Tab
| Option | Description |
|---|---|
| AF For This Bus |
You can specify how you would like arc flash results determined for this bus using AF for this Bus. Calculated: When the bus is faulted, EasyPower the performs arc flash hazard analysis using the calculation method specified in Short Circuit Options. EasyPower uses other settings on this tab as part of the calculations. Excluded: Select to exclude the bus from arc flash reports. An example of when you might select this option is for a bus that is required to model the electrical parameters of the system but does not actually represent a piece of electrical equipment. Other applications include nodes and tap-offs (junctions), where energized work is not required. Forced To: When you select this option, you can enter the incident energy and arc flash boundary for this bus. The incident energy and arc flash boundary values are shown on the one-line and in reports and work permits. This can be used for instances where you need to apply a calculation that is outside the scope of the industry standard calculations. |
| AF Output For This Bus |
You can specify whether to display results on the line side or the load side of the Main protective device of the bus equipment. If the arc flash hazards output for this bus needs to be different from the global option, use this field. The choices are:
|
| Trip Times for this Bus |
You can select the method for determining trip times for this bus by choosing from the following:
|
| Working Distances |
You can specify the working distances shown on the one-line and in reports and work permits.
The units displayed are based on the units selected in Arc Flash Hazard Options on the System tab. For inches, the range is 1-1000. For meters, the range is 0.1 to 1000. |
| Electrode Gap |
You can specify the electrode gap shown on the one-line and in reports and work permits.
|
|
Electrode Configuration |
You can specify the electrode configuration shown on the one-line and in reports and work permits.
Electrodes in Enclosures: Electrodes in Open Air: You can select more than one configuration to represent the multiple types of conditions that can occur for the equipment. EasyPower evaluates each configuration and then provides values for the highest incident energy based on the existing electrode configurations. Annex C in the IEEE 1584-2018 standard describes examples where you might use more than one electrode configuration. Tip: To change the electrode configuration for multiple items on the one-line, select the items in the Database Edit focus and then on the Home tab, click Change > AF Bus Electrode Configuration. Electrode configurations are only applicable to the IEEE 1584-2018 standard. For more information, see Electrode Configuration. |
|
Enclosure Size |
You can specify the enclosure size shown on the one-line and in reports and work permits.
The units displayed are based on the units selected in Arc Flash Hazard Options on the System tab. For inches, the range is .01-1000. For millimeters, the range is 0.1 to 25,000. |
| Labels to Print |
Enter the number of labels you want to print for arc flash hazard analysis. If you enter "0," no labels will print. |
| Comment |
You can type a comment that appears on the arc flash label when it is printed. For example, you could type a location description for the equipment to assist with label placement. |
Accessories Tab
Figure 9: Accessories Tab
| Option | Description |
|---|---|
| Accessories Description | The accessories for distribution equipment types can be specified in the panel, MCC, and bus dialog boxes. You can add or delete the accessory items as needed per equipment. Only the selected items are displayed in the schedule outputs. |
| Meter Data | |
| Note | An accessory note of up to 1,024 characters. |
| Maximum Demand | The maximum demand load at this equipment. |
| Power Factor | The power factor for the equipment. |
| Reading Date | The date the meter was read or the information was gathered. |
| kVA | |
| Safety Factor | Percentage above the kVA that will be multiplied to calculate the new safety factor load. |
| Load with Safety Factor | Load amount after calculating the safety factor. |
| Added (New) Demand Load | User-specified load amount to add to the equipment. |
| Total New Demand Load | Total of the load with safety factor and the added demand load. |
| Total Amps | Amps based on the total demand load. |
Change Management Tab
Note: This information is used in certain specific configurations of EasyPower and is not generally visible.
See Buses and Panels in Change Management Help for details.
Other Tabs
See Common Tabs for information on the Location, Comments, Hyperlinks, or Collected Data tabs.
More Information
| Database Technical Reference | Common Tabs |
| Media Gallery | Configuring the Spreadsheet View |
|
|
|
of (VAA * PF)
of (VA2A - W2A)1/2
of (VAB * PF)
of (VA2B - W2B)1/2
of (VAC * PF)
of (VA2C - W2C)1/2
of (VAA * PF) * DF
of (VA2A - W2A)1/2 * DF
of (VAB * PF) * DF
of (VA2B - W2B)1/2 * DF
of (VAC * PF) * DF
of (VA2C - W2C)1/2 * DF