Two Winding Transformer - Connection Information
Figure 1: Connection Information (ANSI)
Figure 2: Connection Information (IEC)
Figure 3: Connection Information (Single-Phase)
| Option | Description |
|---|---|
|
Uniquely identifies the equipment item. The program automatically assigns a name, but you can change it, if needed. The name can be up to 30 characters long. Special characters such as &!%^\,? cannot be used in the name. For two winding transformers, the program automatically assigns the names TX-1, TX-2, TX-3, and so on. |
|
|
From Bus |
The bus from which the transformer connects, which must already exist on the one-line. Ensure that the From Bus has approximately the same base kV as the transformer's From Rated kV. For reference, the From Bus base kV is displayed next to the bus name. The base kV displays the highest voltage between the current carrying conductors. For 3-phase or line-to-line connected single-phase equipment, the base kV is the line-to-line (LL) voltage. For line-to-neutral (LN) connected single-phase equipment, the base kV is the line-to-neutral voltage. |
|
To Bus |
The bus to which the transformer connects, which must already exist on the one-line. Ensure that the To Bus has approximately the same base kV as the transformer's To Rated kV. For your reference, the From Bus base kV is displayed next to the bus name. The base kV displays the highest voltage between the current carrying conductors. For 3-phase or line-to-line connected single-phase equipment, the base kV is the line-to-line (LL) voltage. For line-to-neutral (LN) connected single-phase equipment, the base kV is the line-to-neutral voltage. |
|
Phase |
The phase type for this item:
|
|
Conn |
The transformer winding connection type, which is either:
If YG or YN is selected, grounding impedances can be entered on the Impedance tab under Grounding. The default settings are D-YG for ANSI, and D-YN with a phase shift of 11 for IEC. These options are not available for single-phase connections. |
|
Center tap connection |
For single-phase, select this check box to indicate that the center tap (neutral) is used. When this option is selected, the secondary side has a distribution system or service type of 1PH-3W. (See 1PH-3W Systems for more information.) The bus or panel connected to the secondary side must also be a 1PH-3W service. Note: In load calculations, loads on L1 and L2 conductors are done separately below the secondary side of a 1PH center-tapped transformer. On the primary side, since it is a 1PH-2W system, the load is summed based on kVA. |
|
Lock Auto-Sizing |
When this check box is selected, this item cannot be automatically sized using SmartDesign™ (the auto-design feature). |
|
Phase Shift: Ref: HV Side |
For IEC transformers, you can specify the phase shift as related to the notations on a clock. Select from 1, 3, 5, 7, 9, or 11. The high voltage side is used as the reference side. This option is available only if the Standard on the transformer is set to IEC and the short circuit calculation method in System options is set to IEC-60909. |
|
(Information Icon) |
The blue information icon indicates that the item must be disconnected to change the value. See Information Icon for more information. |
More Information
- Two Winding Transformer Data
- Database Dialog Box Toolbar
- Two Winding Transformer - Specifications Tab
- Two Winding Transformer - Impedance Tab
- Two Winding Transformer - TCC Tab
- Two Winding Transformer - LTC (Load Tap Changer) Tab
- Two Winding Transformer - Harmonics Tab
- Two Winding Transformer - Stability Tab
- Two Winding Transformer - Reliability Tab
- Two Winding Transformer - Location Tab
- Two Winding Transformer - Comments Tab
- Two Winding Transformer - Hyperlinks Tab
- Two Winding Transformer - Collected Data Tab
- Two Winding Transformer - Media Gallery Tab