Fixing Project Review Warnings

This topic describes how to fix the various project review warnings.

Warning Action
Required Properties

If an item is missing required properties, this error is displayed.

To fix items missing required properties, double-tap the item in the list open the Properties page. All required fields have a yellow background. Type in each of the required properties to clear the warning.

Invalid Values

If an equipment item has invalid values, this means that the wrong type of information was entered on an item property. For example, this could occur if you typed text into a date or number field.

To fix these, double-tap the item in the list to open the Properties page. Invalid value fields display red error text to indicate you need to change the value. Type in the correct value to clear the warning.

Voltage Mismatch

If the system detects a mismatch between the voltage of two connected items, this error is displayed.

To fix this issue, double-tap on the item in the list to open the Properties page, where you can fix the voltage. If the voltage is correct on this item, double-check the voltage on the other connected item.

Disconnected Items

If the app detects that there are equipment items that are either completely or partially disconnected, this error is displayed.

To fix completely disconnected equipment, you can either:

For partially connected equipment, equipment is connected to some equipment but is not fully connected. To find the connections, tap and hold the item in the list to select it, and then tap Go To in the Navigation Bar.

 


Copyright © 2016 EasyPower

Last updated 8/17/2016

OnSite Version 1.3

www.easypower.com